35
Setting the parameters for all models
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
Then determine the value for the output object "smoke alarm: battery warning" should
the battery be nearly flat and when it is to be sent.
Smoke chamber fault warning
If a warning is to be issued when the smoke chamber is faulty, set the function to "yes".
Dirt in the smoke chamber is also indicated as a fault.
Then determine the value for the output object "smoke alarm: smoke chamber fault" in
the event that it is faulty and when it is to be sent.
Heat warning
This function is only available for Salva KNX TH.
If a drastic temperature rise is to be sent to the bus, set the function to "yes". The sys-
tem can then detect the heat from fire, which does not always coincide with smoke
emission.
Set the threshold value and hysteresis for the heat warning. Warning stops when value
falls below the "threshold value minus hysteresis"
Object evaluation
1 = flat • 0 = flat
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Use smoke chamber fault warning
No • Yes
Object evaluation
1 = faulty • 0 = faulty
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Use heat warning
No • Yes
Heat warning threshold value (in 0.1°C)
-300...800; 570
Heat warning hysteresis (in 0.1°C)
0...1100; 50