33
Setting the parameters for all models
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
Alarm
Set the value the smoke alarm object is to have in the event of an alarm, and the cir-
cumstances in which it is to be sent.
Acknowledgeable alarm
The acknowledgeable alarm is active when the smoke alarm is activated. This special
alarm message can, however, be acknowledged and thus "reset" via the bus, e.g. with
a button or a control display. Set the function to "yes" to send an acknowledgeable
alarm with the smoke alarm to the bus.
Then determine the value for the output object "smoke alarm: acknowledgeable alarm"
in the event of an alarm and when it is to be sent. The object is activated when there is
a smoke alarm.
The alarm can only be switched off with the input object "smoke alarm: acknowledge-
able alarm off". Set the value the acknowledgement is to have.
Button acknowledgement
Acknowledge the smoke alarm using the button on the device to turn the acoustic
alarm signal off (see also
Alarm-Stummschaltung (Quittierung)
Object evaluation
1 = active • 0 = active
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Use acknowledgeable alarm
No • Yes
Object evaluation
1 = active • 0 = active
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Evaluation of the acknowledgement object
1 = acknowledgement • 0 = acknowledge-
ment