Temperature and humidity parameters
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
8.4.
Summer Compensation
With the summer compensation the target value for the room temperature can auto-
matically be adapted by cooling at higher outdoor temperatures. The objective is to
prevent a too great a difference between indoor and outdoor temperature in order to
keep the energy consumption low.
Activate the summer compensation.
Using the points 1 and 2, define the outdoor temperature range in which the target
value for the indoor temperature is to be adapted linearly. Then, specify which indoor
temperature target values are to be valid below point1 and above point 2.
Standard values according to DIN EN 60529
Point 1: External temperature = 20°, Target value = 20°C.
Point 2: External temperature = 32°, Target value = 26°C.
Set the send pattern for the summer compensation.
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100
Use summer compensation
No •
Yes
Characteristic curve description:
External temperature point 1 (in 0.1°C
increments)
0 ... 500 ; 200
Outdoor temperature point 2 (in 0.1°C
increments)
0 ... 500 ; 320
below point 1
the target value is (in 0.1°C)
0 ... 500 ; 200
above point 2
the target value is (in 0.1°C)
0 ... 500 ; 260
Send pattern
• periodically
• on change
• on change and periodically
on change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1°C • 2°C • 5°C
Send cycle
(if sent periodically)
5 s ... 2 h; 1 min