-65-
•
An alarm occurs from a Fire zone, the alarm is restored and then a second
alarm occurs from the same zone during the Verified Fire timeout – in this case,
the alarm is reported immediately on receiving the second alarm.
•
An alarm occurs from a Fire zone and a second alarm occurs from an additional
fire zone within the Verified Fire timeout – in this case, the alarm is reported
immediately on receiving the second alarm.
To program the Verified Fire timeout:
1. From the Programming menu, select System Options, Verified Fire [9420].
2. Enter a value between 00 and 60 seconds (00 = disabled).
3. Press
when the desired setting is displayed.
9.21: Battery Type
The battery type shall be defined according to the battery supplied with the system (for example,
if the battery sticker reads 1500 mAh, choose 1.5 Ah, if 3000 mAh, choose 3.0 Ah)
To program the battery type:
1. From the Programming menu, select System Options, Battery Type [9421].
2. Select the battery type.
3. Press
when the desired setting is displayed.