Parameter name
Conditions
Values
Hysteresis
Antistratification function =
enabled
0,5 K
[other values in the range
0,2 … 3
K]
Disable ventilation from bus
no
/ yes
Signal from bus
Disable ventilation from bus =
yes
not inverted
inverted
Fan start delay
0 s
[other values in the range 10 s
…
12 min]
It appears also if the hot-start function is active (through measuring
of the conveying fluid temperature at the battery for the thermal
exchange). The function is active in both seasonal modes (heating
and cooling).
Fan stop delay
0 s
[other values in the range
10 s …
12 min]
The function allows prolonging the operation of the ventilator,
dissipating in the room the residual heat or cool present in battery for
the thermal exchange. The function is active in both seasonal modes
(heating and cooling).
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Fan continuous speed
Control type =
continuous
regulation
1 Byte
CR-T--
[5.001] percentage (0..100%)
71
Fan speed 1
Control type = 1, 2
o 3 speeds
1 Bit
CR-T--
[1.001] switch
72
Fan speed 2
Control type = 2 or
3 speeds
1 Bit
CR-T--
[1.001] switch
73
Fan speed 3
Control type = 3
speeds
1 Bit
CR-T--
[1.001] switch
74
Fan control disable
Disable ventilation
from bus = yes
1 Bit
C-W---
[1.002] boolean
75
Fan manual speed
1 Byte
CRWTU-
[5.010] counter pulses (0…255)
76
Fan speed status
1 Byte
CR-T--
[5.010] counter pulses (0…255)
77
Fan manual active status
1 Bit
CRWTU-
[1.011] state
78
Fan manual speed percentage
1 Byte
R-CT--
[5.1] DPT_Percentage
102
Fan manual speed off status
1 Bit
R-CT--
[1.11] DPT_State
103