Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 69
About the comfort area
You can check whether the temperature and relative humidity values measured in a room are in or out of an
area of climatic comfort defined by the parameters of the dedicated folder and send the corresponding
information on the bus.The area of comfort may be defined for example:
according to the standard DIN 1946, without modifying the default values of the parameters
proposed by the ETS application program for T(min), T(max), R.H.(min) e R.H.(max);
customizing values of the parameters within the range allowed by the application program depending
on the use of the building or rooms, the geographical area, the activities carried out by the occupants
and other factors.
As default values of the area of comfort the following values are considered:
standard maxtemperature 26 °C;
standard mintemperature 20 °C;
standard max relative humidity 65%;
standard min relative humidity 30%.
The defined comfort area refers both to heating and cooling mode.
7.10.2
Calculated psychrometric values
The
Calculated psychrometric values
secondary
folder includes the following parameters:
Dew point temperature
Cyclic sending interval
Min. change of value to send [K]
Temperature to send if no request [°C]
Perceived temperature [°C]
Cyclic sending interval
Min. change of value to send [K]
Condition for displaying the folder: Internal sensors
Relative humidity sensor = enabled.
7.10.2.1
Parameters and communication objects
Parameter name
Conditions
Values
Dew point temperature
disabled
/ enabled
Sending on the bus the dew-point temperature value allows realizing an
anticondensation active protection changing the temperature of the conveying
fluid, if on the bus there is a device for the control of the mixing group. If the
room temperature controller is installed in a room where there is no cooling
(i.e. a bathroom), it is recommended to exclude the room from the control,
setting the parameter to disabled.
Cyclic sending interval
Dew point temperature = enabled
no sending
[other values in the range
30 s … 120
min]
Min. change of value to send [K]
Dew point temperature = enabled,
Cyclic sending interval different
than no sending
0,2 K
/ no sending
[other values in the range 0,2
… 3 K]