Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 67
7.9.2
Humidification
The
Humidification
secondary folder includes the following parameters:
Humidification function
Humidity setpoint [%]
Humidity hysteresis [%]
Cyclic sending interval
Enable humidification from bus
Signal from bus
7.9.2.1
Parameters and communication objects
Parameter name
Conditions
Values
Humidification function
disabled
heating only
cooling only
both heating and cooling
This parameter enables selectively the humidification function.
Humidity setpoint
Humidification different than disabled
35
[range 25
… 45 %]
Humidity hysteresis
0,8 %
[other values in the range 0,5
… 4%]
Cyclic sending interval
no sending
[other values in the range
30 s … 120
min]
Disable humidification from bus
no
/ yes
Signal from bus
Enable humidification from bus = yes
not inverted
/ inverted
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj.
No.
Humidification command
1 Bit
CR-T--
[1.001] switch
88
Humidification control disable
1 Bit
C-W---
[1.002] boolean
89
Relative humidity setpoint for
humidification
2 Byte
RWCTU-
[9.007] humidity (%)
100