Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 63
7.8.5
Scenes
The folder allows the scenes configuration (up to 8), assigning to each one an identification number and the
operating mode to be activated when recalled (e.g. with an ekinex pushbutton or another KNX device with
this function). If
Learning mode = enabled
, receiving a telegram of scene storage determines the association
of the scene to the operating mode currently set on the device.
Important!
Be careful setting the
Download overwrite
parameter. The download of the application program,
particularly after the first commissioning of the system, may cause the loss of the already stored scenes.
The
Scenes
folder includes the following parameters:
Download overwrite
Scene X
Scene number
HVAC mode
Activation delay
Learning mode
Condition:
Temperature control
Settings
Scenes = enabled.
7.8.5.1
Parameters and communication objects
Parameter name
Conditions
Values
Download overwrite
disabled
/ enabled
If Overwrite download = disabled: at the download of the application
on the device, the operating modes previously stored are not
overwritten.
If Overwrite download = enabled: at the download of the application
on the device, the operating modes previously stored are
reprogrammed with the values selected from the HVAC mode
parameter.
Scene X
disabled
/ enabled
This parameter enables the scene X
(X = 1, 2, … 8).
Scene number
Scene X = enabled
1
[range
1 … 64]
HVAC mode
Scene X = enabled
auto /
comfort
/ standby /
economy / building protection
This parameter defines the operating mode of the scene X.
Activation delay
Scene X = enabled
hh:mm:ss (
00:00:00
)
Receiving a telegram that recalls a scene, once elapsed the time
interval set in the Activation delay parameter, the programmed
operating mode is activated.
Learning mode
Scene X = enabled
disabled
/ enabled