Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 52
7.8.3
Cooling
The
Cooling
folder includes the following parameters:
Comfort temp. setpoint [°C]
Standby temperature setpoint [°C]
Economy temp. setpoint [°C]
Building protection temp. setpoint [°C]
Cooling type
Control type
Hysteresis
Cyclic sending interval
Min. change of value to send [%]
PWM cycle time
Proportional band [0,1 K]
Integral time [min]
Anticondensation with probe
Active anticondensation
Flow temperature (project)
Anticondensation hysteresis range
Auxiliary cooling
Disabled from bus
Offset from setpoint
Hysteresis
Cyclic sending interval
Ventilation for auxiliary cooling
Conditions: Temperature control
Settings
Thermostat function = cooling or both heating and cooling.
7.8.3.1
Parameters and communication objects
Parameter name
Conditions
Values
Comfort temp. setpoint [°C]
23
[range
10 … 50]
Standby temperature setpoint [°C]
26
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be >
comfort temperature setpoint.
Economy temp. setpoint [°C]
28
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be >
economy temperature setpoint.
Building protection temp. setpoint [°C]
36
[range
30 … 50]
Cooling type
fan-coils
floor radiant panels
ceiling radiant panels
If in Settings the parameter Thermostat function = both heating and cooling and
Command communication object = unique, the parameter Cooling type is bound to the
choice done for Heating.