Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 21
www.ekinex.com
7.1.1
General
The
General
folder includes the following parameters:
Device operation as
Temperature displayed unit
Default displayed information
Time to return to default display information
Button function level
Time to exit change without saving
Delay after bus voltage recovery
The folder has no secondary folders.
7.1.2
Parameters
Parameter name
Conditions
Values
Device operation as
stand-alone
stand-alone/chrono
slave
If configured as stand-alone/chrono the operating mode can be selected
manually on the device; in that way, the commands received via bus are
ignored. If changing the operating mode the watch symbol is selected, the
commands received via bus are accepted again.
If configured as slave, the room temperature controller receives from a KNX
device (acting as supervisor) HVAC modes, setpont values, etc.
Temperature displayed unit
Celsius
Fahrenheit
Default displayed information
actual temperature
temperature setpoint
The actual temperature is the value by which the device performs the
temperature regulation. It may be the value measured from a single sensor
(internal, from the bus or from an input) or the weighted average of the
temperatures measured by a main sensor and an additional sensor.
The displayed setpoint temperature is that of the operating mode currently
set on the room temperature controller (deduced from the symbol on).
Time to return to default display information
5 s
[other values in the range 10
s … 1 min]
Time interval after which the display automatically switches between the
manually recalled information to the default information.
Button function level
end user
system integrator
This parameter allows you to partially inhibit the functions that can be
recalled using the rockers.
Time to exit change without saving
8 s
[other values in the range 2
s … 12 s]
Time interval without further pressing of the rockers at the end of which the
device exits the procedure without saving the current changes.