Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 39
Parameter name
Conditions
Values
Led second colour XY
fixed
when contact close
status from bus
X = 1, 2; Y= A, B
Off delay
00:00:02:00
[other values in the range
00:00:00:00 … 01.49.13:50]
Value in hh:mm:ss:ff.
Always
Led second colour XY = fixed
off
/ on
Blinking
Led second colour XY = status from bus
no
/ yes
Blinking period / type
Led second colour XY = status from bus,
Blinking = yes
0,25 s on / 0,25 s off
0,25 s on / 0,75 s off
0,5 s on / 0,5 s off
0,75 s on / 0,25 s off
0,5 s on / 1,5 s off
1 s on / 1 s off
1,5 s on / 0,5 s off
1 s on / 3 s off
2 s on / 2 s off
3 s on / 1 s off
Signal from bus
Led second colour XY = status from bus
not inverted
/ inverted
Technical alarm
disabled
/ enabled
It enables the communication object nr. 0 "Technical alarm" that allows to activate an alarm
signal via a bus telegram. The flashing led indicates that the alarm condition is active.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Technical alarm
1 Bit
C--W-
[1.005] alarm
0
Leds intensity percentage
Leds intensity from bus = yes
1 Bit
C--W-
[5.001]
percentage
2
Rocker X- Led first colour A
Led first colour XA = status from
bus
1 Bit
CRWTU-
[1.001] switch
6 (X = 1)
10 (X = 2)
Rocker X- Led second colour
A
Led second colour XA = status
from bus
1 Bit
CRWTU-
[1.001] switch
7 (X = 1)
11 (X = 2)
Rocker X- Led first colour B
Led first colour XB = status from
bus
1 Bit
CRWTU-
[1.001] switch
8 (X = 1)
12 (X = 2)
Rocker X- Led second colour
B
Led second colour LED XB =
status from bus
1 Bit
CRWTU-
[1.001] switch
9 (X = 1)
13 (X = 2)