3.2
Commissioning
For the commissioning the device is provided on the front side (in the area usually occupied by the rockers)
with:
•
a red LED (1) for indication of the active operating mode (LED on = programming, LED off = normal
operation);
•
a pushbutton (2) for switching between the normal and programming operating mode.
Device programming: led (1) and pushbutton (2)
For commissioning the device the following activities are required:
•
make the electrical connections;
•
turn on the bus power supply;
•
switch the device operation to the programming mode by pressing the
programming pushbutton located on the front side of the housing. In this
mode of operation, the programming LED is turned on;
•
download into the device the physical address and the configuration with the
ETS
®
program.
When downloading the application program the display shows "PrOg" and the
flashing symbol of the clock. At the end of the download the operation of the device
automatically returns to normal mode; in this mode the programming LED is turned
off. Now the bus device is programmed and ready for use.
3.2.1
Displaying physical address and firmware release
Once the first addressing is done, you can check anytime the physical address and the firmware release
directly on the device display. In order to display it, press for more than 3 seconds the – (minus) symbol on
the lower rocker and the
symbol on the upper rocker. All segments of the display are turned off;
displaying a physical address only the 3 large digits and the small one are active. The information displayed
in sequence are: the area number (A), the line number (L), the device number (d) and the firmware release
(F). To scroll through the three elements of the physical address press + or –.
1
2