Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 68
7.10
Comfort
The
Comfort
folder includes the following secondary folders:
Comfort area
Calculated psychrometric values
The
Comfort area
and
Calculated psychrometric values
secondary folders appear only if a temperature
sensor and a relative humidity sensor are enabled either in the Internal sensors folder or the External
sensors (from bus) folder.
7.10.1
Comfort area
The
Comfort area
secondary folder includes the following parameters:
Cyclic sending interval
Minimum temperature [°C]
Maximum temperature [°C]
Minimum relative humidity [%]
Maximum relative humidity [%]
Max absolute humidity [g/kg x 0,1]
7.10.1.1
Parameters and communication objects
Parameter name
Conditions
Values
Cyclic sending interval
no sending
[other values in the range
30 s … 120 min]
Minimum temperature [°C]
20
[range 0
… 50]
Maximum temperature [°C]
26
[range
0 … 50]
Minimum relative humidity [%]
30
[range
0 … 100]
Maximum relative humidity [%]
65
[range
0 … 100]
Max absolute humidity [g/kg x 0,1]
115
[range
50… 200]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Comfort state
1 Bit
CR-T--
[1.006] binary
value
80
Comfort state = 1: temperature and relative humidity are inside the defined comfort area.
Comfort state = 0: temperature and relative humidity are outside the defined comfort area.