The C.O.
77 – Fan manual status
allows to evaluate the actual fan speed; the C.O.
78 – Fan manual active
status
contains the information about automatic (=0, not active) or manual (=1, active) operating mode. By
modifying the C.O.
76 – Fan manual speed
, the fan automatically switches to the setpoint speed; to return to
automatic mode (A), the supervisor must exit from manual mode by modifying the C.O.
78 – Fan manual
active status
(=0, not active).
Accepted values for C.O.s 76 and 77 depend on the number of speeds set in ETS.
If
Control Type
parameter in Ventilation folder is = 1, 2 or 3 speeds, C.O.s with DPT [5.010 counter] accept
the following values:
= 0: OFF
= 1: speed 1
= 2: speed 2 (if
Control Type
> 1 speed)
= 3: speed 3 (if
Control Type
> 2 speed)
If
Control Type
parameter in Ventilation folder is = continuous regulation, the values of the C.O.s with DPT
[5.010 counter] match the following percentage of the maximum speed:
= 0: OFF
= 1: 20%
= 2: 40%
= 3: 60%
= 4: 80%
= 5: 100%