7.2
Internal sensors
The
Internal sensors
folder includes the following parameters:
Temperature sensor
Relative humidity sensor
7.2.1
Parameters
Parameter name
Conditions
Values
Temperature sensor
enabled
disabled
The temperature sensor is enabled as default.
When the sensor is disabled, the corresponding folder disappears from the
main tree structure of the application program; in this case to have available
again the functions for Temperature control you have to enable Room
temperature in the External sensors (from bus) folder or set Input X = [AI]
temperature sensor (X = 1, 2) in the Inputs folder.
Relative humidity sensor
disabled
enabled
The relative humidity sensor is disabled as default.
When the sensor is disabled, the functions that require the value of relative
humidity are available only if you enable Relative humidity in the External
sensors (from bus) folder.
When the sensor is enabled, the corresponding folder appears in the main
tree structure of the application program.
7.2.2
Temperature sensor
The
Temperature sensor
secondary folder appears only if the corresponding sensor is enabled in the folder
Internal sensors
and includes the following parameters:
Filter type
Temperature offset
Minimum change of value to send [K]
Cyclic sending interval
Threshold 1
Threshold 2
7.2.2.1
Parameters and communication objects
Parameter name
Conditions
Values
Filter type
Temperature sensor = enabled
low
medium
high
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Temperature offset
Temperature sensor = enabled
0°C
[range -5°C … +5°C]
Minimum change of value to send [K]
Temperature sensor = enabled
0,5
[range 0 …5]
If the parameter is set to 0 (zero),no value is sent after a change.