STP-iXA3306 Series Turbomolecular Pump
MT-82E-001-H
Page 72
OPER
A
T
ION
4.9.3
Rotation INHIBIT signal
When using rotation INHIBIT signal, short-circuit the "INHIBIT ENABLE IN" signal. Relations between
rotation INHIBIT signal input and pump operation state are shown in Table 23.
Signal input
Pump operation
After short-circuit of rotation INHIBIT input
signal (A), the START operation is
performed (B).
INHIBIT IN
Close
Open
START operation
●
The pump accelerates when the START
operation is performed (B).
After the START operation (A), the rotation
INHIBIT input signal is short-circuited (B).
INHIBIT IN
Close
Open
START operation
●
The pump does not accelerate when the
START operation is performed (A).
●
The pump accelerates when the rotation
INHIBIT input signal is short-circuited (B).
The rotation INHIBIT input signal is opened
(A) during acceleration or normal
operation.
INHIBIT IN
Close
Open
START operation
●
The pump decelerates and stops when the
rotation INHIBIT input signal is opened (A).
●
After the operation (A), the pump continues
deceleration and stops even by
short-circuiting the rotation INHIBIT input
signal (B). However, when the START signal
is input, the pump will accelerate.
Table 23 - Rotation INHIBIT signal input
A B
A B
A B
Содержание STP-iXA3306B
Страница 12: ...STP iXA3306 Series Turbomolecular Pump MT 82E 001 H Page x PAGE x This page intentionally blank ...
Страница 24: ...STP iXA3306 Series Turbomolecular Pump MT 82E 001 H Page 12 INTRODUCTION 1 This page intentionally blank ...
Страница 66: ...STP iXA3306 Series Turbomolecular Pump MT 82E 001 H Page 54 INSTALLATION 3 This page intentionally blank ...
Страница 176: ...STP iXA3306 Series Turbomolecular Pump MT 82E 001 H Page 164 MAINTENANCE AND INSPECTION 8 This page intentionally blank ...