Firmware V6.6.9
29.07.2020
140/147
•
•
•
•
12 Specifications of System Centre and SIOX
12.1 Electrical data
System centre
SIOX extension module
Operating voltage
230 V AC, 200 - 265 V AC, 47/63 Hz
9 V / 24 V DC
supply via the system centre
Rated power
36 W
3.1 W
Leakage current over PE
(protective earth)
max 1 mA
Digital inputs
1)
2 x 230 V AC floating output,
for external alarms (inputs IN.1 and IN.2)
12 x 230 V AC / 24 V, floating output,
S0 meter input internally adjustable using jumper;
for details, see chapter
.
Relay outputs
1)
3 x changeover contact for signalling system, floating
output:
2 x 230 V AC, min. >= 10 mA, load type:
max. 6 A (ohmic) / max. 3 A (inductive) / (24 V
DC / max. 5 A DC)
For outputs PRIO.1 and PRIO.2 with bistable
relays and 5 minutes response delay after
shutdown of the device.
1 x 230 V AC min. 5 V / 10 mA max 230 V
AC / 6 A max. 24 V DC / 5 A
For output AUX, e.g. for audible signalling unit
4 x normally open contact, 250 V AC,
floating output, min 10 mA
Load type: ohmic: max. 6 A, inductive:
max. 3 A, cos phi = 0.4
4 x changeover contact, 250 V AC,
floating output, min 10 mA
Load type: ohmic: max. 6 A, inductive:
max. 3 A, cos phi = 0.4
Manual control switch
-
The SIOX extension modules have manual
control switches so that the regulation can be
overridden in emergency operation, see chapter
IOX manual / automatic mode selection
Field bus interface
CAN bus, floating output
-
Data ports
1x data port for SIOX
Internal interface for the system centre
3 x seriell RS232
1x seriell RS485
-
Archive memory
Compressor run times, starts,
quotas, messages
-
Real-time clock
With power reserve and lithium cell (for details, see
""Transport and storage")
Accuracy: typical 12 minutes per year at 25 °C
-
Monitoring function
Watchdog
For safety reasons and to guarantee important functions (e.g. alarm forwarding to a service centre via
modem) only accessories approved by Eckelmann AG (see chapter
permitted to be used with the system centre.
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
Overvoltage category II / soiling degree 2:
All connections of the device provided for operation with
230 V AC supply voltage
must
be wired with the same phase conductor. 400 V AC between
neighbouring connection terminals is
not
permitted!
Overvoltage category II / soiling degree 2:
Different phase conductors may be used. 400 V AC
between neighbouring connection terminals is permitted!