Firmware V6.6.9
29.07.2020
14/147
•
•
•
•
•
•
•
•
Interfaces - bottom
1 x COMBICON terminal 91..95 (power supply) and 1 x RJ45 port (data cable) for connecting up to max. 4
optional SIOX extension modules.
COM1 / modem port for remote access via modem using a host system or the connection of a service PC
for serial direct cable connection
COM2 - RS232 port for M-bus components (e.g. energy meters).
USB Host/Slave
CAN bus interface (CAN1) for connection of the E*LDS components
e.g. case controllers in the UA 300 / UA 400 series, VS 3010, VS 3010 BS, VS 3010 CT, FS 3010, VS 300
pack controllers, PC-CAN bus adapter.
CI 4500 only:
- Second CAN bus interface (CAN2) for use as CAN bus repeater.
Interfaces - left side
Only CI 4100 or higher:
- COM3/MODBUS - RS485 interface on COMBICON terminal for direct connection of UA 30 Rx compact
controllers / LDS1 gateways / Dixell
so that the RS232 interface (COM2) can be used for external controllers.
- COM4 - RS232 interface for Danfoss AHT / Wurm AHT external controllers
Only CI 4400 or higher:
- Ethernet / LAN
See chapter System centre tasks, page 18 for further information about configuration and range of
functions
and see chapter Pin / terminal assignment system centre / SIOX,
page 57 for the pin assignment
System centre and SIOX connection / terminal assignment
.