Firmware V6.6.9
29.07.2020
116/147
Alarm signalling other
Entry
Default
AUX relay
Function XXX
The multi-function relay AUX must be set to
PRIOX3, .. or PRIOX9 so that it can be used as
alarm relay!
For details about the configuration, chapter
Multi-function relay AUX, page 30.
Horn,
alarm relay PrioX3,
PrioX4, PrioX5, PrioX6,
PrioX7, PrioX8, PrioX9
Modem reset
GLT modem changeover
Horn
Alarm relay stop
Stop alarm relay PRIO1/PRIO2:
Y: Relays are only deactivated when the cause
for the alarm has been rectified and the alarm
has been acknowledged
N: Relays are deactivated when the horn is
switched off
Y/N
Y
Test alarm
Message text XXX
Message text of the test alarm
-
Test alarm
Priority XXX
Message priority of the test alarm
1..99
1
Test alarm trip
Button for tripping the test alarm
-
-
Alarm destination 4..15 - read-only!
The screen contains the following parameters:
Alarm destination 4..15
Entry
Default
Description
Description of the alarm destination, e.g. Service 2
-
-
Telephone number
Telephone number of the alarm destination
-
-
Priority A
Priority A
-
-
Priority B
Priority B
-
-
Time range
Messages are never, within, outside or always
transmitted in the time range.
Possible values are: Never, Within, Outside, Always
-
Never
Menu 4-1-8 - Date / Time
The entry screen for configuration of the date and time of the system centre is called using this
button. This makes the date and time available system-wide for all E*LDS components; it is the so-called "time
server".
It must be checked before the configuration of the multi-function relay AUX that no conflict with the
existing configuration / wiring is produced by the change of the settings.
For example, a possible conflict could be that a horn is already connected to the multi-function relay
AUX and is used for audible alarm signalling!
The extended alarm destinations can only be configured using the LDSWin PC software; the menu
only shows the settings configured there!