actions can occur for a time interval. Therefore, a correct maximum shed load should be set for each load
shedding stage used to guarantee optimum operation of the LSM.
Minimum operating time
A minimum operating time can be configured using this parameter. The minimum operating time specifies the
time that a stage must at least be active before it is permitted to be shed again. If any time > 0 is parametrised,
this is decisive whether any shedding for the stage is performed. If any limitation of shedding should not be
used, this time must be parametrised with 0.
Minimum load shed time
A minimum load shed time can be configured using this parameter. The minimum load shed time specifies the
time that a stage must at least be shed for. It may be loaded again afterwards. If the time is parametrised to 0, it
has no influence on the function of the LSM.
Maximum time (load shed time
A maximum load shed time can be configured using this parameter. This time starts with the shedding of a
stage. If the configured maximum load shed time is reached, the stage is loaded again irrespective of the
current power demand and load shed state. The times are recorded and processed separately for each stage.
With parametrisation to 0, this function is deactivated and the load shed time is not limited.
Load shed output
A load shed output must be configured for each load shedding stage. The appropriate consumer is shed using
this. A stage or a consumer is shed using an active load shed output. If no output is configured for a stage, no
shedding takes place for this stage.