XSTORAGE HOME 3P INSTALLATION MANUAL
MN700009EN August 2020 www.eaton.com
00
Title
Guards or covers can be removed only 10 minutes after disconnecting the inverter from the power supply to
allow its components to cool down and any static electricity storage devices to discharge.
As soon as it is switched off, the surface of the equipment could be hot, therefore great care must be taken.
In the event of fire, CO2 foam extinguishers must be used, and self-vacuum systems must be used to put
out fires in enclosed spaces.
Should the noise level exceed legal limits, the working area must be circumscribed and all the people who
have access to the area must wear ear defenders or ear plugs.
The noise level produced by the inverter in normal working conditions is: < 50 db.
During the installation process, special attention must be paid to fixing the equipment and its components.
During this stage, circumscribing and preventing access to the installation area is recommended.
A first aid kit must be provided. Do not underestimate burns or wounds.
An electric shock can be fatal.
Avoid touching internal or external normally live parts whilst the system is powered on.
Cables and connections must always be secured, in good conditions, insulated and suitably sized.
The equipment contains capacitors that store static electricity, which could produce dangerous electric
discharges. Make sure that the devices have discharged their energy before carrying out any work on the
equipment
Clothing and Personal protective equipment (PPE)
Eaton certified installers are recommended to wear clothing and PPE provided by their employer. Operators
must not wear clothes or accessories that could start fires or produce static electricity or, generally
speaking, any item of clothing that could affect personal safety. When carrying out any operation on the
equipment, clothes and instruments must be suitably insulated.
Ex: class 0, category RC insulated gloves
Maintenance operations must be strictly carried out with the equipment disconnected from the grid, from
the PV generator and from the batteries.
Eaton certified installers must NOT access the equipment with bare feet or wet hands.
The maintenance engineer must always ensure that nobody else is able to reset or operate the equipment
during the maintenance stages and must report any fault or deterioration caused by wear or by aging, in
order to restore the correct safety conditions.
The Eaton certified installer or maintenance engineer must always pay attention to the working environment,
to ensure it is well lit and has a suitable escape route.
3.3 Protection from electric shock