Installing the IAC
3-8
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
Top View with Small Bracket
Existing
Screw
Bracket
from Kit
M4 Screw and
Four Washers
from Kit
UPS
IAC
Front View with Large
Angle Bracket
Nut from Kit
Existing Hinge
M4 Screws
from Kit
Bracket from Kit
UPS
IAC
Figure 3-5. 40–80 kVA UPS to IAC Joining Brackets
24.
Locate the large angle bracket, M4 screws, and large nut from the field kit. Place
one end of the bracket over the bolt on the bottom side of the lower hinge on the
IAC, and loosely secure the bracket to the hinge with the large nut (see
Figure 3-5).
25.
Align the holes in the other end of the bracket with the holes in the bottom
right-hand side of the UPS (see Figure 3-5). Secure the bracket with the M4 screws
from the field kit.
26.
Secure the large nut on the IAC hinge.
27.
Proceed to paragraph 3.3.2.
28.
Remove the right-hand screw from the top right-hand door hinge of the UPS
cabinet and the left-hand screw from the top left door hinge of the IAC.