POWER WIRING INSTALLATION NOTES
013106
B
164201590---4
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
13 of 13
Installation Information
A-31
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
15.
The MIS and SLB breakers on the 80 kVA, 120 kVA, and 160 kVA IACs are adjustable trip
breakers and are set to maximum at the factory. During installation these breakers must be
adjusted for the site requirements using the dial on each breaker. The MIS and SLB
breakers on the 40 kVA IAC are non-adjustable.
16.
The continuous current (Ir) values for the corresponding lettered adjustment setting
marked on the MIS and SLB breakers are listed in Table T.
Table T. MIS and SLB Continuous Current (Ir) Settings
Breaker
Setting
80 kVA Continuous
Current (Ir)
120 kVA Continuous
Current (Ir)
160 kVA Continuous
Current (Ir)
208V
480V
208V
480V
208V
480V
A
250
100
250
100
250
250
B
300
125
300
125
300
300
C
350
150
315
150
315
350
D
400
160
350
160
350
400
E
—
175
400
175
400
—
F
—
200
450
200
450
—
G
—
225
500
225
500
—
H
—
250
600
250
600
—
Содержание Powerware 9390 IAC-B
Страница 145: ......
Страница 146: ...164201590C 164201590 C...