Installation Information
A-61
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
BackUp Control (Pull Chain) Wiring Terminations
From
To
UPM 1 TB2–1 (Bldg Alm 2)
IAC TB1–5 (MOB 1 Aux 2 NO)
UPM 2 TB2–1 (Bldg Alm 2)
IAC TB1–9 (MOB 2 Aux 2 NO)
UPM 1 TB2–2 (Bldg Alm Rtn)
UPM 2 TB2–4 (On Bypass Common)
IAC TB1–6 (MOB 1 Aux 2 Common)
IAC TB1–10 (MOB 2 Aux 2 Common)
UPM 1 TB2–1 (Bldg Alm 2)
UPM 1 TB2–3 (Byp)
UPM 1 TB2–2 (Bldg Alm 2 Rtn)
UPM 1 TB2–4 (Byp Common)
UPM 2 TB2–1 (Bldg Alm 2)
UPM 2 TB2–3 (Byp)
UPM 2 TB2–2 (Bldg Alm 2 Rtn)
UPM 2 TB2–4 (Byp Common)
013106
B
164201590---7
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
1
2
3
4
5
7
8
6
TB1
9
10
TB2
1+1 PARALLEL REDUNDANT
CONFIGURATION
BACKUP CONTROL
(PULL CHAIN) WIRING
UPM 1
1
2
3
4
5
7
8
6
9
10
1
2
3
4
5
7
8
6
TB1
9
10
IAC
1
2
3
4
5
7
8
6
TB1
9
10
TB2
1
2
3
4
5
7
8
6
9
10
UPM 2
INTERFACE AND CONTROL WIRING
INSTALLATION NOTES AND
TERMINAL LOCATIONS
6 of 7
SPLICE
JUMPERS
JUMPERS