1 of 13
POWER WIRING INSTALLATION NOTES
013106
B
164201590---4
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-19
EATON
Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual
S
164201590 Rev C
powerware.com
Table D
.
INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9390 IAC 100–160 kVA 208V(Maintenance Bypass Configuration)
Units
Rating 50/60 Hz
Basic Unit Rating
KVA
100
120
160
Input and Bypass Input
Output
VOLTS
VOLTS
208
208
208
208
208
208
AC Input to Optional RIB
(Line-up-and-Match or Standalone Installation)
(3) Phases, (1) Ground
A
AMPS
300
360
480
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
3/0
(2)
4/0
(2)
400
(2)
AC Input to Maintenance Bypass
(Line-up-and-Match or Standalone Installation)
(single-feed without BIB or RIB, or
dual-feed with BIB and RIB)
(3) Phases, (1) Neutral---if required, (1) Ground
B
AMPS
278
333
444
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
3/0
(2)
4/0
(2)
400
(2)
AC Input to Maintenance Bypass
(Line-up-and-Match or Standalone Installation)
(single-feed with BIB, or single-feed
with BIB and RIB)
(3) Phases, (1) Neutral---if required, (1) Ground
B
AMPS
300
360
480
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
3/0
(2)
4/0
(2)
400
(2)
AC Output from Optional RIB to UPS
(Standalone Installation)
(3) Phases, (1) Ground
C
AMPS
300
360
480
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
For contractor-supplied wiring, refer to the applicable
Powerware 9390 UPS Installation and Operation manual,
listed in paragraph 1.5. Wiring for line-up-and-match
installation is factory-supplied.
AC Output from Optional BIB to UPS
(Standalone Installation)
(3) Phases, (1) Neutral---if required, (1) Ground
D
AMPS
278 (Dual-Feed)
300 (Single-Feed)
333 (Dual-Feed)
360(Single-Feed)
444 (Dual-Feed)
480 (Single-Feed)
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
For contractor-supplied wiring, refer to the applicable
Powerware 9390 UPS Installation and Operation manual,
listed in paragraph 1.5. Wiring for line-up-and-match
installation is factory-supplied.
AC Input from UPS
(Standalone Installation)
(3) Phases, (1) Neutral---if required, (1) Ground
E
AMPS
300
333
444
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
For contractor-supplied wiring, refer to the applicable
Powerware 9390 UPS Installation and Operation manual,
listed in paragraph 1.5. Wiring for line-up-and-match
installation is factory-supplied.
AC Output to Critical Load
(Line-up-and-Match or Standalone Installation)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
AMPS
278
333
444
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
3/0
(2)
1/0
(1)
400
(2)
NOTE:
Callout letters
A, B, C, D, E,
and
F
map to drawing 164201590---3, sheets 1 of 11
through 9 of 11.