59
9. Ethernet/IP
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
The old format of the message is as follows
(OPTCQ option board):
Table 119.
Field
Data
Service Code
10h
Class Code
A0h
Instance Number
YYh
Attribute ID
XXh
Attribute Data
Parameter-specific
9.2.3.2 Assembly instance selector object, class 0xBE
The Assembly Instance Selector Object is a vendor-specific
object available in the OPTCQ option board and the OPTE9.
It allows the user to get and set the input and output
instances used.
The OPTE9 option board will automatically change the
current assembly instances by what is requested in the
connection opening. This means that it is not mandatory to
pre-set assembly instances.
Table 120. Assembly instance selector object
Class name
Assembly instance selector object
Class identifier
190d / BEh
Class attributes
Id
Access rule
Name
Datatype
Description
–
–
–
–
–
Class services
Id
Name
Description
–
–
–
Instance attributes
Id
Access rule
Name
Datatype
Description
3
Get/Set
InputInstance
USINT
Input assembly instance
4
Get/Set
OutputInstance
USINT
Output assembly instance
Instance services
Id
Name
Description
14d
0Eh
Get_Attribute_Single
Used to read single attribute value.
16d
10h
Set_Attribute_Single
Used to write a single attribute value.
9.2.3.2.1. Instance attributes
Instance attribute “Inputinstance”
This attribute shows the currently active (or what was last
used) input assembly instance id.
Instance attribute “Outputinstance”
This attribute shows the currently active (or what was last
used) output assembly instance id.
9.2.3.2.2. Services
Instance service “Get_Attribute_Single”
The format of the message is as follows.
Table 121.
Field
Data
Service Code
0Eh
Class Code
BEh
Instance Number
01h
Attribute ID
03h or 04h
Instance service “Set_Attribute_Single”
The format of the message is as follows:
Table 122.
Field
Data
Service Code
10h
Class Code
BEh
Instance Number
01h
Attribute ID
03h or 04h
Attribute Data
(Assembly number)
9.2.3.2.3. Rejection of set_attribute_single request
If an I/O connection has been established with a master
through the Forward_Open request and a successful
response, any request to set the selected assembly through
the Assembly Instance Selector object is rejected. These
attributes may only be changed when no I/O connection is
established, i.e. before the Forward_Open request.
9.2.3.3 Motor control mode object, class 0xA1
The Motor Control Mode Object is a vendor-specific object
available in the OPTE9 which more clearly indicates to the
user which motor control mode is used, and allows the user
to configure this mode.
Содержание OPTE9