7. Modbus TCP
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
Process data master -> Slave (max 22 bytes)
Table 20. Fieldbus process data IN
Address 16-bit*
32-bit
Name
Range/Type
2001
2051 = High data
2052 = Low data
FB Control Word
Binary coded
2002
–
In case of 16-bit,
FB General Control Word (High data)
Binary coded
2003
2053 = High data
2054 = Low data
FB Speed Reference
0…10000 %
2004
2055 = High data
2056 = Low data
FB Process Data In 1
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2005
2057 = High data
2058 = Low data
FB Process Data In 2
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2006
2059 = High data
2060 = Low data
FB Process Data In 3
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2007
2061 = High data
2062 = Low data
FB Process Data In 4
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2008
2063 = High data 2064 = Low data
FB Process Data In 5
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2009
2065 = High data
2066 = Low data
FB Process Data In 6
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2010
2067 = High data
2068 = Low data
FB Process Data In 7
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2011
2069 = High data
2070 = Low data
FB Process Data In 8
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
Control word bits
See Chapter 12 “APPENDIX 2 – CONTROL AND STATUS WORD” for control word bit descriptions.
7.1.3.5.3. FB Process data out
Values in these indexes can be only read, not written.
Table 21. Fieldbus process data OUT
Address 16-bit*
32-bit
Name
Range/Type
2101
2151 = High data
2152 = Low data
FB Status Word
Binary coded
2102
–
In case of 16-bit,
FB General Status Word (High data)
Binary coded
2103
2153 = High data
2154 = Low data
FB Actual Speed
0…10000 %
2104
2155 = High data
2156 = Low data
FB Process Data Out 1
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2105
2157 = High data
2158 = Low data
FB Process Data Out 2
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2106
159 = High data
2160 = Low data
FB Process Data Out 3
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2107
2161 = High data
2162 = Low data
FB Process Data Out 4
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2108
2163 = High data
2164 = Low data
FB Process Data Out 5
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2109
2165 = High data
2166 = Low data
FB Process Data Out 6
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2110
2167 = High data
2168 = Low data
FB Process Data Out 7
See Chapter 11 “APPENDIX 1 – PROCESS DATA”
2111
2169 = High data
2170 = Low data
FB Process Data Out 8
See Chapter 11 “APPENDIX 1 – PROCESS DATA”