
19
7. Modbus TCP
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
7.1.3.5 Holding registers
The values can be read with function code 3. Modbus registers are mapped to drive IDs as follows:
Table 18. Defined holding registers
Address range
Purpose
Access type
See
R/W
Max R/W size
0001 – 2000
Eaton Application ID´s
16bit
Table 19
RW
30/30
2001 – 2011
FBProcessDataIN
16bit
Table 20
RW
11/11
2051 – 2070
FBProcessDataIN
32bit
1)
Table 20
RW
20/20
2101 – 2111
FBProcessDataOUT
16bit
Table 21
RO
11/0
2151 – 2170
FBProcessDataOUT
32bit
1)
Table 21
RO
20/0
2200 – 10000
Eaton Application ID´s
16bit
Table 19
RW
30/30
10501 – 10530
IDMap
16bit
Figure 28
RW
30/30
10601 – 10630
IDMap Read/Write
16bit
Table 22
RW
30/30
2)
10701 – 10760
IDMap Read/Write
32bit
1)
Table 22
RW
30/30
20001 – 40000
Eaton Application ID's
32bit
1)
Table 19
RW
30/30
40001 – 40005
Operation day counter
16bit
Table 25
RO
5/0
40011 – 40012
Operation day counter
32bit
1)
Table 24
RO
2/0
40101 – 40105
Resettable operation day counter
16bit
Table 27
R, Write 1 to first index to reset
5/0
40111 – 40112
Resettable operation day counter
32bit
Table 26
RO
2/0
40201 – 40203
Energy counter
16bit
Table 29
RO
3/0
40211 – 40212
Energy counter
32bit
Table 28
RO
2/0
40301 – 40303
Resettable energy counter
16bit
Table 31
R, Write 1 to first index to reset
3/0
40311 – 40312
Resettable energy counter
32bit
Table 30
RO
2/0
40401 – 40430
Fault history
16bit
Table 32
RO
30/0
40501
Communication timeout
16bit
Table 34
RW
1/1
40511-40568
Fault history with 16 bit fault codes 16bit
Table 33
RO
30/0
1) Not supported in current version. See chapter 5.
7.1.3.5.1. Eaton application IDs
Application IDs are parameters that depend on the drive’s
application. These parameters can be read and written by
pointing the corresponding memory range directly or by
using the so-called ID map (more information below). The
easiest way to read a single parameter value or parameters
with consecutive ID numbers is to use a straight address.
It is possible to read 30 consecutive ID addresses. Notice
that the operation will fail if even one of the consecutive IDs
do not exist.
Parameters which have 32 bit value can be read from their
own range. For example, if you want to read the value for
ID 864 (FB Status Word), the address must be set to 21726.
This address value comes from values: 20000 + ((ID -1) * 2).
The ID value is reduced with one because of zero-based
addressing and the result is multiplied with 2 because
one 32 bit value will take two (16 bit) addresses.
Table 19. Parameter IDs
Address
range
Purpose
ID range
0001-2000
16 bit application parameters
1-2000
2200-10000
16 bit application parameters
2200-10000
20001-40000
32 bit application parameters
1-20000
7.1.3.5.2. FB process data in
The process data fields are used to control the drive
(e.g. Run, Stop, Reference, Fault Reset) and to quickly read
actual values (e.g. Output frequency, Output current, Fault
code). The values in these indexes can be read and written.
The fields are structured as follows.
Содержание OPTE9
Страница 1: ...FPO OPTE9 Dual port ethernet option board installation manual...
Страница 88: ...This Page Intentionally Left Blank...
Страница 89: ...This Page Intentionally Left Blank...