c. Automatic disconnection of the supply in case of
loss of continuity of the protective conductor.
The cross-sectional area of every protective earthing
conductor which does not form part of the supply cable
or cable enclosure must, in any case, be not less than:
– 2.5mm
2
if mechanical protection is provided or
– 4mm
2
if mechanical protection is not provided
The earth fault protection inside the AC drive protects only
the drive itself against earth faults in the motor or the motor
cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive,
fault current protective switches may not function properly.
WARNING
Do not perform any voltage withstand tests on any part
of the AC drive. There is a certain procedure according to
which the tests must be performed. Ignoring this
procedure can cause damage to the product.
otee:
N
You can download the English and French product
manuals with applicable safety, warning and caution
information from www.eaton.com/drives.