6. Commissioning
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
6.1.6.1 Modbus TCP
See Chapter “7.1.3.5.11. Modbus Communication and
connection timeout”.
6.1.6.2 Profinet IO and EtherNet/IP
For these protocols, this value is considered as an additional
timeout. The protocol itself has timeout mechanism. When it
notices that the connection has been lost, a fault activation
is started. If communication timeout value is zero, the fault
is activated immediately, otherwise the fault activates after
a specified time. If the connection is reopened before the
specified time has elapsed, no fault is activated.
6.1.7 Profinet IO – Name of station
The Profinet IO “Name of Station” parameter can be set
via 9000XDrive or NCIPConfig. Other possibility is to set
this name by writing it from the PLC. The parameter can
be found from the same list as protocol selection and IP
settings. The parameter is not visible in the keypad, only in
the PC tools.
If no name is set, the option board will generate a
temporary name. The name is formed from the drive power
unit serial number or, if that value is not available, from the
option board MAC address and from slot ID. The format is:
opt-<slot>-<unique identifier>.
Example: opt-e-v00000030473
Example: opt-e-mac-002199ff0329
6.1.8 EIP Input and output instance
These parameters will show what instances are being used
now. The instances actually used are taken from the IO
connection open request. So, although these values are
parameters they act more like monitoring values.
6.1.9 EIP product code offset
This value can be used to differentiate drives for the PLC
program. For example, if one drive is running a different
application (with different parameters) than other drives,
this offset in the product code will enable the PLC to use a
different EDS file to read those parameters from this drive.
Remember that if you change this value, you need also to
change the EDS file used or change the product code value
in your EDS file.
Table 13. Mode values
Mode value
Description
Normal
Option board will identify itself as OPTE9
(depends on fieldbus protocol)
9000x Mode
Option board will identify itself as old C-series counterpart
and will emulate selected features. Currently only when using
EtherNet/IP protocol.