44
9. Ethernet/IP
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
9.2 Common industrial objects implemented by the OPTE9
9.2.1 Cip common required objects
9.2.1.1 Identity object, class 0x01
The Identity Object provides identification of and general
information about the device.
Table 89. Identity object
Class name
Identity Object
Class identifier
1
Class attributes
Id
Access rule
Name
Datatype
Description
1
Get
Revision
UINT
Class revision (1)
2
Get
Max Instance
UINT
Maximum instance number (1)
3
Get
Number of Instances
UINT
Number of object instances (1)
Class services
Id
Name
Description
1
Get_Attributes_All
Get all attributes
14
d
0E
h
Get_Attribute_Single
Get single attribute
Instance attributes
Id
Access rule
Name
Datatype
Description
1
Get
Vendor ID
UINT
Vendor identification
2
Get
Device Type
UINT
General type of product
3
Get
Product Code
UINT
Product identification
4
Get
Revision
STRUCT of
Revision of the item the Identity Object
represents
Major Revision
USINT
Minor Revision
USINT
5
Status
WORD
Summary status of device
6
Serial number
UDINT
Serial number of the device
7
Product Name
SHORT STRING
Human readable identification
Id
Name
Description
Instance services
1
Get_Attributes_All
Get all attributes
5
Reset
Only reset type 0
14
d
0E
h
Get_Attribute_Single
Get single attribute
9.2.1.1.1. Instance attributes
Instance attribute “Vendor ID”
This number is assigned to vendors of CIP devices by the
ODVA user organization. The vendor ID for Eaton Plc is
01BB
h
(443
d
).
Instance attribute “Device Type”
This attribute indicates which device profile is implemented
by the device. For Eaton drives this device number is
02
h
(“AC Drive” profile).
Instance attribute “Product Code”
This attribute reveals the vendor-assigned product code for a
particular product within a device type.
Separate products must have different product codes if their
configuration and/or runtime options are different.
OPTE9 will return the product code value based on the drive
where the option board has been installed. This value can
also be modified with the “Product Code Offset” parameter
(see Chapter 6 “Commissioning”).
When the “Mode” setting is set to “SVX/SPX Mode”, setting
the “Product Code Offset” has no affect and OPTE9 will
emulate the OPTCQ option board and return value to 2.
Table 90. Drive type specific product code values
Drive type
Product code base value
SVX/SPX drives
1200
Emulating OPTCQ
2
Содержание OPTE9
Страница 1: ...FPO OPTE9 Dual port ethernet option board installation manual...
Страница 88: ...This Page Intentionally Left Blank...
Страница 89: ...This Page Intentionally Left Blank...