8. Profinet IO
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
the FBFixedStatusWord.
8.4.3.1.9. Vendor-specific fbgeneralcontrolword
FB General Control Word is 16-bit in length and it is
completely application-dependent.
8.4.3.1.10. Vendor-specific fbgeneralstatusword
FB General Status Word is 16-bit in length and it is
completely application-dependent.
8.4.3.1.11. Vendor-specific process data
The Process Data variables are vendor-specific variables
that can be communicated to and from the drive. There
can be up to eight Process Data variables communicated
in a single telegram. Values sent from the option board
to the master are called ProcessDataOut variables, while
the values sent from the master to the option board
are called ProcessDataIn variables. The contents of the
ProcessDataOut variables can be parameterised in the drive
using a feature known as Fieldbus Process Data mapping.
See the drive’s Application Manual for further details.
8.4.3.2 PROFIDrive standard telegram 1 and
vendor-specific variants
These telegrams use the PROFIDrive-defined control
word, status word, speed setpoint value and speed actual
value. It is also possible to use up to eight Process Data
fields. Using these telegrams, the process data fields are
communicated as 16-bit values.
Table 67. PROFIDrive standard telegram
Telegram no.
Telegram
1
Standard telegram 1
102
Standard telegram 1 + PD1
103
Standard telegram 1 + PD[1..2]
104
Standard telegram 1 + PD[1..3]
100
Standard telegram 1 + PD[1..4]
105
Standard telegram 1 + PD[1..5]
106
Standard telegram 1 + PD[1..6]
107
Standard telegram 1 + PD[1..7]
101
Standard telegram 1 + PD[1..8]
8.4.3.2.1. Setpoint data
Standard telegram 1 – setpoint data
Table 68. PROFIDrive standard telegram 1 – setpoint data
Standard telegram 1
Additional process Data (16-bit each)
STW1
(16-bit
NSOLL_A
(16-bit)
PDI1 PDI2 PDI3 PDI4 PDI5 PDI6 PDI7 PDI8
STW1 (16-bit) (See 8.4.3.1.1. STW1 – Control Word 1 31)
NSOLL_A (16-bit) (See 8.4.3.1.3. PROFIDrive speed setpoint
value NSOLL_A)
PDI1-PDI8 (See 8.4.3.1.11. Vendor-specific Process Data)
8.4.3.2.2. Actual data
Standard telegram 1 – actual data
Table 69. PROFIDrive standard telegram 1 – actual data
Standard telegram 1
Additional process Data (16-bit each)
ZSW1
(16-bit)
NIST_A
(16-bit)
PDO1 PDO2 PDO3 PDO4 PDO5 PDO6 PDO7 PDO8
ZSW1 (16-bit) (See8.4.3.1.2. ZSW1 – Status Word 1 32)
NIST_A (16-bit) (See 8.4.3.1.4. PROFIDrive speed actual
value NIST_A)
PDO1-PDO8 (See 8.4.3.1.11. Vendor-specific Process Data)
8.4.3.3 Vendor-specific telegram 1 and its variant
These telegrams use the vendor-specific control word,
status word, speed setpoint value and speed actual value.
It is also possible to use up to eight vendor-specific Process
Data fields. Using these telegrams, the process data fields
are communicated as 16-bit values.
Table 70. Vendor-specific telegram 1
Telegram no.
Telegram
108
Vendor-specific Telegram 1
109
Vendor-specific Telegram 1 + PD1
110
Vendor-specific Telegram 1 + PD[1..2]
111
Vendor-specific Telegram 1 + PD[1..3]
112
Vendor-specific Telegram 1 + PD[1..4]
113
Vendor-specific Telegram 1 + PD[1..5]
114
Vendor-specific Telegram 1 + PD[1..6]
115
Vendor-specific Telegram 1 + PD[1..7]
116
Vendor-specific Telegram 1 + PD[1..8]
8.4.3.3.1. Setpoint data
Vendor specific telegram 1 – setpoint data
Table 71. Vendor-specific telegram 1 – setpoint data
Vendor-specific telegram 1
Additional process data (16-bit each)
FB
Fixed
CW
(16-bit)
FB
Speed
Reference
16-bit)
PDI1 PDI2 PDI3 PDI4 PDI5 PDI6 PDI7 PDI8
FB Fixed CW (16-bit) (See 8.4.3.1.5. Vendor-specific
FBFixedControlWord)
FB Speed Reference (16-bit) (See 8.4.3.1.6. Vendor-specific
FBSpeedReference) PDI1-PDI8 (See 8.4.3.1.11. Vendor-specific
Process Data)