7. Modbus TCP
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
7.1.4 Quick setup
Following these instructions, you can easily and fast set up
your Modbus for use:
In the AC drive application: Choose Fieldbus as the active
control place (see drives User’s Manual).
In the master softwaree:
1.
Set the settings in the master software
2. Set the Control Word to ‘0’ (2001)
3. Set the Control Word to ‘1’ (2001)
4.
Drive’s status is RUN
5. Set the Reference value to ‘5000’ (50.00%) (2003)
6.
Actual speed is 5000 (25.00 Hz if MinFreq is 0.00 Hz and
MaxFreq is 50.00 Hz)
7. Set the Control Word to ‘0’ (2001)
8.
Drive’s s
tatus is STOP
7.2 Modbus TCP – Example messages
7.2.1 Example 1 – Write process data
Write the process data 42001…42003 with command 16
(Preset Multiple Registers).
Command master – Slavee:
Address
01 hex Slave address 1 hex (= 1)
Function
10 hex
Function 10 hex (= 16)
Data
Starting address HI 07 hex Starting address 07D0 hex (= 2000)
Starting address LO D0 hex
No. of registers HI 00 hex Number of registers 0003 hex (= 3)
No. of registers LO 03 hex
Byte count
06 hex Byte count 06 hex (= 6)
Data HI
00 hex Data 1 = 0001 hex (= 1).
Setting control word run bit to 1.
Data LO
01 hex
Data HI
00 hex Data 2 = 0000 hex (= 0).
Data LO
00 hex
Data HI
13 hex
Data 3 = 1388 hex (= 5000),
Speed reference to 50.00%
Data LO
88 hex
Error
check
CRC HI
C8 hex CRC field C8CB hex (= 51403)
CRC LO
CB hex
Message framee:
01 10 07 D0 00 03 06 00 01 00 00 13 88 C8 CB
The reply to Preset Multiple Registers message is the echo
of 6 first bytes.
Answer slave – Mastere:
Address
01 hex Slave address 1 hex (= 1)
Function
10 hex Function 10 hex (= 16)
Data
Starting address HI
07 hex Starting address 07D0 hex (= 2000)
Starting address LO
D0 hex
No. of registers HI
00 hex Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
Error
check
CRC HI
80 hex CRC 8085 hex (= 32901)
CRC LO
85 hex
Reply framee:
01
10
07
D0
00
03
80
85
7.2.2 Example 2 – Read process data
Read the Process Data 42103…42104 with command 4
(Read Input Registers).
Command master – Slavee:
Address
01 hex Slave address 1 hex (= 1)
Function
04 hex Function 4 hex (= 4)
Data
Starting address HI
08 hex Starting address 0836 hex (= 2102)
Starting address LO
36 hex
No. of registers HI
00 hex Number of registers 0002 hex (= 2)
No. of registers LO
02 hex
Error
check
CRC HI
93 hex
CRC LO
A5 hex CRC 93A5 hex (= 37797)
Message framee:
01
04
08
36
00
02
93
A5
The reply to the Read Input Registers message contains the
values of the read registers.
Answer slave – Mastere:
Address
01 hex Slave address 1 hex (= 1)
Function
04 hex Function 4 hex (= 4)
Data
Byte count
04 hex Byte count 4 hex (= 4)
Data HI
13 hex Speed reference = 1388 hex
(=5000 => 50.00%)
Data LO
88 hex
Data HI
09 hex Output Frequency = 09C4 hex
(=2500 =>25.00Hz)
Data LO
C4 hex
Error
check
CRC HI
78 hex
CRC LO
E9 hex CRC 78E9 hex (= 30953)