Appendix C:
Using DNP Mapping for IQ 250/260 IQ 250/260 Meter
C-4
IB02601006E
www.eaton.com
Object 30 – Analog Inputs (Secondary Readings) - Read via Class 0 only
Object Point Var Description
Format Range
Multiplier
Units
Comments
30
0
4
Meter Health
sint16
0 or 1
N/A
None
0 = OK
30
1
4
Volts A-N
sint16
0 to 32767
(150 / 32768)
V
Values
above
150V
secondary read 32767.
30
2
4
Volts B-N
sint16
0 to 32767
(150 / 32768)
V
30
3
4
Volts C-N
sint16
0 to 32767
(150 / 32768)
V
30
4
4
Volts A-B
sint16
0 to 32767
(300 / 32768)
V
Values
above
300V
secondary read 32767.
30
5
4
Volts B-C
sint16
0 to 32767
(300 / 32768)
V
30
6
4
Volts C-A
sint16
0 to 32767
(300 / 32768)
V
30
7
4
Amps A
sint16
0 to 32767
(10 / 32768)
A
Values
above
10A
secondary read 32767.
30
8
4
Amps B
sint16
0 to 32767
(10 / 32768)
A
30
9
4
Amps C
sint16
0 to 32767
(10 / 32768)
A
30
10
4
Watts, 3-Ph total
sint16
-32768
to
+32767
(4500 / 32768)
W
30
11
4
VARs, 3-Ph total
sint16
-32768
to
+32767
(4500 / 32768)
VAR
30
12
4
VAs, 3-Ph total
sint16
0 to +32767
(4500 / 32768)
VA
30
13
4
Power Factor, 3-Ph total
sint16
-1000 to +1000 0.001
None
30 14 4
Frequency
sint16
0
to
9999 0.01
Hz
30 15 4 Positive Watts, 3-Ph,
Maximum Avg Demand
sint16 -32768 to
+32767
(4500 / 32768)
W
30 16 4 Positive VARs, 3-Ph,
Maximum Avg Demand
sint16 -32768 to
+32767
(4500 / 32768)
VAR
30
17 4 Negative Watts, 3-Ph,
Maximum Avg Demand
sint16 -32768 to
+32767
(4500 / 32768)
W
30
18 4 Negative VARs, 3-Ph,
Maximum Avg Demand
sint16 -32768 to
+32767
(4500 / 32768)
VAR
30
19
4 VAs, 3-Ph, Maximum Avg
Demand
sint16 -32768 to
+32767
(4500 / 32768)
VA
30
20
4
Angle, Phase A Current
sint16
-1800 to +1800 0.1
degree
30
21
4
Angle, Phase B Current
sint16
-1800 to +1800 0.1
degree
30
22
4
Angle, Phase C Current
sint16
-1800 to +1800 0.1
degree
30
23
4
Angle, Volts A-B
sint16
-1800 to +1800 0.1
degree
30
24
4
Angle, Volts B-C
sint16
-1800 to +1800 0.1
degree
30
25
4
Angle, Volts C-A
sint16
-1800 to +1800 0.1
degree
30
26
4
CT numerator
sint16
1 to 9999
N/A
none
CT ratio =
30
27
4
CT multiplier
sint16
1, 10, or 100
N/A
none
(numerator * multiplier) /
denominator
30
28
4
CT denominator
sint16
1 or 5
N/A
none
30
29
4
PT numerator
SINT16 1 to 9999
N/A
none
PT ratio =
30
30
4
PT multiplier
SINT16 1, 10, or 100
N/A
none
(numerator * multiplier) /
denominator
30
31
4
PT denominator
SINT16 1 to 9999
N/A
none
30
32
4
Neutral Current
SINT16 0 to 32767
(10 / 32768)
A
For 1A model, multiplier is
(2 / 32768) and values
above 2A secondary read
32767
.
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...