Chapter 8:
IQ 250/260 Meter Programming the IQ 250/260
www.eaton.com
IB02601006E
8-1
8
Programming the IQ 250/260
Overview
The IQ 250/260 Meter can be configured using either the meter Face Buttons (Menu, Enter, Down and Right) or IQ
250/260 Configuration Software. To connect to the meter for software configuration, use the RS485 port (Com 2)
on the back panel of the meter.
The 250/260T must be configured with the IQ 250/260 Configuration Software, using the RS485 port, since it does
not have a front panel.
This chapter contains instructions for programming the IQ 250/260 Meter and Transducer using the IQ 250/260
Configuration Software.
Connecting to the IQ 250/260
1. Open IQ 250/260 Configuration Software.
2. Click the
Connect
icon on the Title bar or
Connection>Quick Connect
.
3.
If you are connecting to the IQ 250/260 through your PC
:
a. Make sure the
Serial Port
radio button is selected.
b. Enter
Device Address
(1-249).
c. Select
Baud Rate
from the pull-down menu.
d. Select the port you are using from the pull-down menu. The
Available Ports/All Ports
radio buttons determine which port selections
the menu displays.
e. Select
Modbus RTU
from the
Protocol
pull-down menu.
f. Select
Flow Control
:
None
or
Hardware
.
g. Select
Echo Mode
:
No Echo
or
Statis Echo
.
If you are connecting to the Meter through the Power Xpert® Gateway
:
a. Make sure the
Network
radio button is selected.
b. Enter
Device Address
(1-247).
c. Enter the Gateway’s
IP Address
.
d. Enter
Network Port
.
e.
Protocol
defaults to
Modbus TCP
.
4. Click the
Connect
button. You will see the
Device Status
screen, shown on the right.
NOTE for IQ 250/260 Transducer
:
When the
IQ 250/260T
is powered up, for
10
seconds
you can connect to the meter using the
Factory Initial Default Settings (even if the Device
Profile has been changed). After 10 seconds,
the Device Profile reverts to the actual Device Profile
in use.
Factory Initial Default Settings
Baud Rate:
9600
Port:
COM1
Protocol:
Modbus RTU
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...