Appendix C:
Using DNP Mapping for IQ 250/260 IQ 250/260 Meter
C-2
IB02601006E
www.eaton.com
Application Layer
In the IQ 250/260, DNP Lite supports the
Read
function,
Write
Function, the
Direct Operate
function and
the
Direct Operate Unconfirmed
function.
•
The
Read
function (
code 01
) provides a means for reading the critical measurement data from
the IQ 250/260 meter. This function should be posted to read object 60 variation 1, which will
read all the available Class 0 objects from the DNP Lite register map. See register map in Section
C.6. In order to retrieve all objects with their respective variations, the qualifier must be set to ALL
(0x06). See Section C.7 for an example showing a read Class 0 request data from the IQ
250/260.
•
The
Write
function (
code 02
) provides a mean for clearing the Device restart bit in the Internal
Indicator register only. This is mapped to Object 80, point 0 with variation 1. When clearing the
restart device indicator use qualifier 0. Section C.7 shows the supported frames for this function.
•
The
Direct Operate
function (
code 05
) is intended for resetting the energy counters and the
demand counters (minimum and maximum energy registers). These actions are mapped to
Object 12, point 0 and point 2, that are seen as a control relay.
The relay must be operated (On) in 0 msec and released (Off) in 1 msec only. Qualifiers 0x17 or
x28 are supported for writing the energy reset. Sample frames are shown in Section C.7.
•
The
Direct Operate Unconfirmed
(or
Unacknowledged
) function (
code 06
) is intended for
asking the communication port to switch to Modbus RTU protocol from DNP Lite. This switching
is seen as a control relay mapped into Object 12, point 1 in the IQ 250/260. The relay must be
operated with qualifier 0x17, code 3 count 0, with 0 millisecond on and 1 millisecond off, only.
After sending this request the current communication port will accept Modbus RTU frames only.
To make this port go back to DNP protocol, the unit must be power-recycled. Section C.7 shows
the constructed frame to perform DNP to Modbus RTU protocol change.
Error Reply
In the case of an unsupported function, or any other recognizable error, an error reply will be generated
from the IQ 250/260 to the Primary station (the requester). The Internal Indicator field will report the type
of error: unsupported function or bad parameter.
The broadcast acknowledge and restart bit, are also signaled in the internal indicator but they do not
indicate an error condition.
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...