A
IQ 250/260 Meter
Appendix B:
Modbus Mapping
2B42 - 2B42
11075 - 11075
Pulse Output Test Power
UINT16
bit-mapped
ddvvvvvv vvvvvvvv
This register is Writeable in privileged session only.
Simulates constant Power for the Pulse Output under test.
Format is same as Kt settings for Pulse Output.
"V" is raw value in Wh/pulse from 0 to 9999. "dd"=decimal
point position: 00=0.XXXX, 01=X.XXX, 10=XX.XX, 11=
X.XXX.
1
2B43 - 2B46
11076 - 11079
Reserved
Reserved
4
2B47 - 2B47
11080 - 11080
Input 1 Accumulator, Scaled
UINT16
0 to 9999
1
2B48 - 2B48
11081 - 11081
Input 2 Accumulator, Scaled
UINT16
0 to 9999
1
2B49 - 2B49
11082 - 11082
Input 3 Accumulator, Scaled
UINT16
0 to 9999
1
2B4A - 2B4A
11083 - 11083
Input 4 Accumulator, Scaled
UINT16
0 to 9999
1
2B4B - 2B4B
11084 - 11084
Output 1 Accumulator, Scaled
UINT16
0 to 9999
1
2B4C - 2B4C
11085 - 11085
Output 2 Accumulator, Scaled
UINT16
0 to 9999
1
2B4D - 2B4D
11086 - 11086
Output 3 Accumulator, Scaled
UINT16
0 to 9999
1
2B4E - 2B4E
11087 - 11087
Output 4 Accumulator, Scaled
UINT16
0 to 9999
1
2B4F - 2B78
11088 - 11129
Reserved
Reserved
42
Block Size:
58
read-only
2B3F - 2B3F
11072 - 11072
Status of card
UINT16
bit-mapped
----cf-- --------
Flag fields:
c=calibration not good; f=configuration error
1
2B40 - 2B78
11073 - 11129
Reserved
UINT16
Reserved
57
Block Size:
58
read-only
2EDF - 2EE0
12000 - 12001
Option Card 1, Input 1 Accumulator
UINT32
0 to 999999999
number of transitions
2
2EE1 - 2EE6
12002 - 12007
Option Card 1, Inputs 2-4 Accumulators
UINT32
0 to 999999999
number of transitions
6
2EE7 - 2EE8
12008 - 12009
Option Card 1, Output or Relay 1 Accumulator
UINT32
0 to 999999999
number of transitions
2
2EE9 - 2EEE
12010 - 12015
Option Card 1, Output or Relays 2-4
UINT32
0 to 999999999
number of transitions
6
2EEF - 2EF6
12016 - 12023
Option Card 2 Inputs Accumulators
UINT32
0 to 999999999
number of transitions
8
2EF7 - 2EFE
12024 - 12031
Option Card 2 Outputs Accumulators
UINT32
0 to 999999999
number of transitions
8
Block Size:
32
write-only
4E1F - 4E1F
20000 - 20000
Reset Max/Min Blocks
UINT16
password5
1
4E20 - 4E20
20001 - 20001
Reset Energy Accumulators
UINT16
password5
1
4E21 - 4E21
20002 - 20002
Reserved
1
4E22 - 4E22
20003 - 20003
Reserved
1
4E23 - 4E23
20004 - 20004
Reserved
1
4E24 - 4E24
20005 - 20005
Reserved
1
4E25 - 4E25
20006 - 20006
Reserved
1
4E26 - 4E26
20007 - 20007
Reserved
1
4E27 - 4E2E
20008 - 20015
Reserved
Set to 0.
8
Block Size:
16
Resets Block9
Set to 0.
Reserved Registers
These are unscaled counts. See option card section for
scaled versions.
Input accumulators count either or both transitions; output
accumulators count both transitions.
Unused accumulators always read 0.
Commands Section4
Accumulators Block
resolution is 1, 10, 100, 1000,
10000, or 100000 counts
Disabled accumulators always read 0.
Data and Control Block--
Analog Out 0-1mA / Analog Out 4-20mA (Note 15)
www.eaton.com
IB02601006E MM-15
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...