IQ 250/260 Meter
Appendix B:
Modbus Mapping
First Overlay
write only in PS update mode
80E8 - 80E8
33001 - 33001
Input#1 - 2 bindings & logging enables
UINT16
bit-mapped
-------- 2222 1111
One nibble for each input.
Assuming "abcd" as the bits in each nibble:
"a": select this input for EOI (End Of Interval)pulse sensing.
"b": log this input when pulse is detected
"cc": Input event trigger mode - Contact sensing method;
00 = none; 01 = open to close; 10 = close to open; 11 = any
change.
1
80E9 - 80E9
33002 - 33002
Relay #1 Delay to Operate
UINT16
0.1 second units
Delay to operate the relay since request.
1
80EA - 80EA
33003 - 33003
Relay #1 Delay to Release
UINT16
0.1 second units
Delay to release the relay since request.
1
80EB - 80F0
33004 - 33009
Reserved
UINT16
Set to 0.
6
80F1 - 80F1
33010 - 33010
Relay #2 Delay to Operate
UINT16
0.1 second units
Delay to operate the relay since request.
1
80F2 - 80F2
33011 - 33011
Relay #2 Delay to Release
UINT16
0.1 second units
Delay to release the relay since request.
1
80F3 - 8108
33012 - 33033
Reserved
UINT16
Set to 0.
22
8109 - 8109
33034 - 33034
Input Accumulators Scaling
UINT16
bit-mapped
-------- 22221111
1
810A - 810A
33035 - 33035
Relay Accumulators Scaling
UINT16
bit-mapped
-------- 22221111
1
810B - 8126
33036 - 33063
Reserved
Set to 0.
28
Block Size:
63
First Overlay
write only in PS update mode
80E8 - 80E8
33001 - 33001
Input#1 - 4 bindings & logging enables
UINT16
bit-mapped
44443333 22221111
One nibble for each of the 4 inputs.
Assuming "-bcc" as the bits in each nibble:
"b": Log this input when pulse is detected
"cc": Input event trigger mode - Contact sensing method;
00 = none; 01 = open to close; 10 = close to open; 11 = any
change.
1
80E9 - 80E9
33002 - 33002
Source for Pulse Ouput#1
UINT16
enumeration
-----ppp ----vvvv
"
ppp"
(Phase)
: 000 = none, 001 = Phase A, 010 = Phase
B, 011 = Phase C, 100 = All Phases, 101 = Pulse from
EOI(End Of Interval).
"vvvv"(Value) :
0000= none,
0001 = Wh,
0010 = +Wh,
0011 = -Wh,
0100= Varh,
0101 = +Varh,
0110 = -Varh,
0111 = VAh,
1000= Received Wh,
1001= Delivered Wh,
1010= Inductive Varh,
1011 = Capacitive Varh
1
80EA - 80EA
33003 - 33003
Kt [Wh/pulse] factor for Pulse Output#1
UINT16
bit-mapped
ddVVVVVV VVVVVVVV
"V…V" = not scaled energy value per pulse, from 0 to
9999.
"dd"= decimal point position: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
1
80EB - 80EC
33004 - 33005
Output#2 Assignment and Kt
UINT16
2
80ED - 80EE
33006 - 33007
Output#3 Assignment and Kt
UINT16
2
* 4 bits per accumulator
* 0xF disables the accumulation
* 0-5 = power of divisor for the scaled accumulator
Example: count=12456, 4bits=3:
divisor=103=1000 & scaled accumulator=12.
Settings Registers for Digital I/O Pulse Output Card
Same as Output #1.
Settings Registers for Digital I/O Relay Card
Same as Output #1.
www.eaton.com
IB02601006E MM-22
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...