A
IQ 250/260 Meter
Appendix B:
Modbus Mapping
7D43 - 7D44
32068 - 32069
High value of source register for output#1
Value read from the source register at which High nominal
current will be output. Example: for the 4-20mA card, if this
register is programmed with 750, then the current output will
be 20mA when the value read from the source register is
750.
2
7D45 - 7D46
32070 - 32071
Low value of source register for output#1
Value read from the source register at which Low nominal
current will be output. Example: for the 4-20mA card, if this
register is programmed with 0, then the current output will
be 4mA when the value read from the source register is 0.
2
7D47 - 7D4C
32072 - 32077
Analog output#2 format, register, max & min
6
7D4D - 7D52
32078 - 32083
Analog output#3 format, register, max & min
6
7D53 - 7D58
32084 - 32089
Analog output#4 format, register, max & min
6
7D59 - 7F3E
32090 - 32575
Reserved
Set to 0.
486
Block Size:
512
write only in PS update mode
80E7 - 80E7
33000 - 33000
Class ID of the Option Card 2 Settings
UINT16
bit-mapped
-------- cccctttt
Which class (cccc) and type(tttt) of card the Option Settings
for Card 2 apply to. See note 19.
1
80E8 - 8126
33001 - 33063
Settings for Option Card 2, First Overlay -- see
below
63
8127 - 8326
33064 - 33575
Settings for Option Card 2, Second Overlay -- see
below
512
Block Size:
576
First Overlay
write only in PS update mode
80E8 - 80E8
33001 - 33001
Slave address
UINT16
1~247 (for Modbus)
1~65534 (for DNP)
none
Slave address of the unit. The communication capable card
is always a master.
Set to 0 when an analog board is installed.
1
80E9 - 80E9
33002 - 33002
Speed and format
UINT16
bit-mapped
-abcde--fghijklm
Bps: a=57600; b=38400; c=19200; d=14400; e=9600
Stop bits 'f': cleared 1 stop bit, set 2 stop bits
Parity: g=even; h=odd; i=none
Data bits: j=8; k=7; l=6; m=5
Set to 0 when an analog board is installed.
1
80EA - 80EA
33003 - 33003
Reserved
UINT16
bit-mapped
Set to 0.
1
80EB - 80EB
33004 - 33004
Protocol
UINT16
bit-mapped
-------- -----ppp-
ppp= 100 =DNP3 Lite; 010=Ascii Modbus; 001=Rtu
Modbus
Set to 0 when an analog board is installed.
1
80EC - 80EC
33005 - 33005
Reply delay
UINT16
0 to 65535
milliseconds
Delay to reply to a Modbus transaction after receiving it.
Set to 0 when an analog board is installed
1
80ED - 8126
33006 - 33063
Reserved
Set to 0.
58
Block Size:
63
Programmable Settings for Option Card 2
Overlays for Option Card 2 Programmable Settings
Settings Registers for any communication capable card, including analog cards
Option Card 2 Setups Block
Register assignments depend on which type of card is in the slot. See overlays below.
Register assignments depend on which type of card is in the slot. See overlays below.
Depends on the format parameter
Same as analog output #1.
Same as analog output.#1.
Same as analog output #1.
Depends on the format parameter
www.eaton.com
IB02601006E MM-21
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...