A
IQ 250/260 Meter
Appendix B:
Modbus Mapping
7536 - 7536
30007 - 30007
Operating Mode Screen Enables
UINT16
bit-mapped
-------- eeeeeeee
eeeeeeee = op mode screen rows on/off, rows top to
bottom are bits low order to high order.
1
753E - 753E
30015 - 30015
User Settings Flags
UINT16
bit-mapped
---g--nn srpdywf-
g = enable alternate full scale bar graph current (1=on,
0=off)
nn = number of phases for voltage & current screens
(3=ABC, 2=AB, 1=A, 0=ABC)
s = scroll (1=on, 0=off)
r = password for reset in use (1=on, 0=off)
p = password for configuration in use (1=on, 0=off)
d = daylight saving time changes (0=off, 1=on)
y = diagnostic events in system log (1=yes, 0=no)
w = power direction (0=view as load, 1=view as generator)
f = flip power factor sign (1=yes, 0=no)
1
753F - 753F
30016 - 30016
Full Scale Current (for load % bar graph)
UINT16
0 to 9999
none
If non-zero and user settings bit g is set, this value replaces
CT numerator in the full scale current calculation.
1
7540 - 7547
30017 - 30024
Meter Designation
ASCII
16 char
none
8
7548 - 7548
30025 - 30025
Reserved
Set to 0.
1
7549 - 7549
30026 - 30026
COM2 setup
UINT16
bit-mapped
----dddd -ppp-bbb
1
754A - 754A
30027 - 30027
COM2 address
UINT16
1 to 247
none
1
754B - 754B
30028 - 30028
Limit #1 Identifier
UINT16
0 to 65535
Use Modbus address as the identifier (see notes 7, 11, 12).
1
754C - 754C
30029 - 30029
Limit #1 Out High Setpoint
SINT16
-200.0 to +200.0
0.1% of full scale
Setpoint for the "above" limit (LM1), see notes 11-12.
1
754D - 754D
30030 - 30030
Limit #1 In High Threshold
SINT16
-200.0 to +200.0
0.1% of full scale
Threshold at which "above" limit clears; normally less than
or equal to the "above" setpoint; see notes 11-12.
1
754E - 754E
30031 - 30031
Limit #1 Out Low Setpoint
SINT16
-200.0 to +200.0
0.1% of full scale
Setpoint for the "below" limit (LM2), see notes 11-12.
1
754F - 754F
30032 - 30032
Limit #1 In Low Threshold
SINT16
-200.0 to +200.0
0.1% of full scale
Threshold at which "below" limit clears; normally greater
than or equal to the "below" setpoint; see notes 11-12.
1
7550 - 7554
30033 - 30037
Limit #2
SINT16
5
7555 - 7559
30038 - 30042
Limit #3
SINT16
5
755A - 755E
30043 - 30047
Limit #4
SINT16
5
755F - 7563
30048 - 30052
Limit #5
SINT16
5
7564 - 7568
30053 - 30057
Limit #6
SINT16
5
7569 - 756D
30058 - 30062
Limit #7
SINT16
5
756E - 7572
30063 - 30067
Limit #8
SINT16
5
7573 - 7582
30068 - 30083
Reserved
Set to 0.
16
7583 - 75C2
30084 - 30147
Reserved
Set to 0.
64
75C3 - 75E5
30148 - 30182
Reserved
Set to 0.
35
75E6 - 75E6
30183 - 30183
Programmable Settings Update Counter
UINT16
0-65535
Increments each time programmable settings are changed;
occurs when new checksum is calculated.
1
75E7 - 7626
30184 - 30247
Reserved for Software Use
Set to 0.
64
Block Size:
248
dddd = reply delay (* 50 msec)
ppp = protocol (1-Modbus RTU, 2-Modbus ASCII, 3-DNP)
bbb = baud rate (1-9600, 2-19200, 4-38400, 6-57600)
Same as Limit #1.
Same as Limit #1.
Same as Limit #1.
www.eaton.com
IB02601006E MM-17
Содержание IQ 250
Страница 2: ......
Страница 22: ...3 6 IB02601006E www eaton com Chapter 3 Mechanical Installation IQ 250 260 Meter...
Страница 38: ...4 16 IB2601006E www eaton com Chapter 4 Electrical Installation IQ 250 260 Meter...
Страница 100: ...A 2 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Main Menu Screens Sheet 1...
Страница 101: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 3 Operating Mode Screens Sheet 2...
Страница 102: ...A 4 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter Reset Mode Screens Sheet 3...
Страница 103: ...Appendix A IQ 250 260 Meter IQ 250 260 Navigation Maps www eaton com IB02601006E A 5 Con guration Mode Screens Sheet 4...
Страница 104: ...A 6 IB02601006E www eaton com Appendix A IQ 250 260 Navigation Maps IQ 250 260 Meter...
Страница 134: ...A IQ 250 260 Meter Appendix B Modbus Mapping www eaton com IB02601006E MM 28...