52
Replacement of common parts
EATON ICUBE 2.0
UM.ICUBE2.0.SG.0822 August 2022 www.eaton.com
8.3 The electronic lock
The electronic locks are installed on the front and rear doors. Be noted that the fixing screws of the electronic
lock are the Pozidriv screw, a dedicated spanner is provided in the accessory kit.
Figure 8 .3
Replacement steps: Unplug input network cable
→
loosen the upper and lower fixing screws
→
install
new electronic lock
→
adjust the upper and lower location
→
plug in the cable, pay attention to the
corresponding line.
8.4 Smoke sensor
The smoke sensor is installed inside of the top of the cabinet, divides into upper and lower parts, the wire
terminal is the base, the sensor head is the main body, the main body and base are connected by rotating
locking pin.
Implementation steps are as follows:
1. Turn the smoke sensor body 30 ° counterclockwise in the direction of the as shown arrows and there is no
need to change the base.
Set new smoke sensor and tighten clockwise.
If it is necessary to change the stand, remove the wiring screws as shown in the figure: 8.4 below.
Figure 8 .4 Smoke sensor