Installation
EATON ICUBE 2.0
UM.ICUBE2.0.SG.0822 August 2022 www.eaton.com
3.2.5 Communication to Temp/Humidity sensors
Figure 3 .12
Connect the cable (T/H2 identifier) remaining on the top of cabinet 1 to T/H2 IN port in front of the cabinet 2
Connect the cable (T/H3 identifier) remaining on the top of cabinet 2 to T/H3 IN port in front of the cabinet 3
Connect the cable (T/H4 identifier) remaining on the top of cabinet 3 to T/H4 IN port in front of the cabinet 4
Connect the cable (T/H5 identifier) remaining on the top of cabinet 4 to T/H5 IN port in front of the cabinet 5
Connect the cable (T/H6 identifier) remaining on the top of cabinet 5 to T/H6 IN port in front of the cabinet 6
Connect the cable (T/H7 identifier) remaining on the top of cabinet 6 to T/H7 IN port in front of the cabinet 7
The network cable is as follows: (choose a network wire, other similar types)
Figure 3 .13
Temp and humidity sensor address setting
Cabinet 1 address sets as 1, Cabinet 2 address sets as 2 and so on .
Address \ Location
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
Address no. 1
0
0
0
0
0
0
Address no. 2
1
0
0
0
0
0
Address no. 3
0
1
0
0
0
0
Address no. 4
1
1
0
0
0
0
Address no. 5
0
0
1
0
0
0
Address no. 6
1
0
1
0
0
0
Address no. 7
0
1
1
0
0
0
Figure 3 .14
Example for Adress No. 2