8

Conformity with standards

They have been designed, manufactured and 
tested according to the state of the art and to 
DIN EN ISO 9001:2015 and  
EN ISO/IEC 80079-34:2011.

The apparatus is conform to the standards 
specified in the EC-Declaration of conformity, 
enclosed separately.

Field of application

The plugs and sockets GHG 511 are suitable for 
use in Zones 1 and 2 as well as in Zones 21 and 
22 in accordance with IEC/EN 60079-10-1 and 
IEC/EN 60079-10-2.

The enclosure materials employed, including 
the exterior metal parts, are made of high- quali-
ty materials which ensure a corrosion protec-
tion and resistance to chemical substances 
corresponding to the requirements in a “normal 
industrial atmosphere”:

   

- impact resistant polyamide 

 

- glass-fibre reinforced polyester 

 

- special steel AISI 316 L

When used in extremely aggressive atmosphere, 
you can request additional information on the 
chemical resistance of plastics used in your 
responsible Cooper Crouse-Hinds branch.

5 Use/Properties

The GHG 511 plugs and sockets are used for  
the power supply of local controls with varying 
locations, as well as of electrical installations, 
mobile machinery and driving gear in hazardous 
areas.

The plugs and sockets can also be used in a 
„normal industrial area“. The low-voltage plugs 
and sockets GHG 511 are fitted with a load 
switch and can be used up to max. 16 A (see 
technical data). The plugs and sockets can 
generally be used for the voltage range laid  
down in IEC/EN 60309 (e.g. UN 400V that 
corresponds to the voltage range 380-415V).

The apparatus connected to the plug shall 
be suitable for the applied mains voltage.

In order to switch on the socket, the plug is 
inserted, pushed fully home and then turned 
through approx. 45° to the right. Thereby the 
plug is locked in the socket (see page 15, fig. 1).

For switching off and pulling the plug, proceed 
in inverse order.

After separating the plug from the socket, the 
latter shall be closed with the hinged cover and 
secured with the bayonet ring. The plug can be 
pushed into the socket and pulled out of it only 
whilst the socket is switched off.

In order to ensure the socket’s type of 
protection acc. to the type label also with the 
plug being inserted, the bayonet ring of the plug 
(see page 15, fig. 2, item 2) is turned to its stop 
onto the socket.

The data  as per point 3 and 4 will have to 
be taken into account with the use. 
Applications other than described are not 
permitted without Cooper Crouse-Hinds’s 
prior written consent.

For the operation, the instructions stated in 
section 7 of the operating instructions will 
have to be observed.

From time to time, the locking function 
protecting against inappropriate use e. g. of 
industrial plugs in zone 1 has to be checked.

In the open air, the plugs must be kept with the 
plug opening (pin side) pointing downwards or  
be closed with protective plug caps available  
as an optional extra (see general catalogue).

The user alone is responsible for the 
appropriate use of this plug and socket 
system in consideration of the basic 
conditions existing at the plant  
(see technical data).

After a short in the circuit, the functioning of 
the plug and socket system and of the plugs 
has to be checked.

Since the switch contacts can no more be 
checked because of the flameproof enclo-
sure, the complete switch insert (flange 
socket) will have to be replaced after 
repeated short circuits.

Weight: 

(catalogue version)

Wall socket

3-pole GHG 511 43

approx. 1.10 kg

Plug

3-pole GHG 511 73

approx. 0.27 kg / GHG 543 - approx. 0.23 kg

Coupler

3-pole GHG 511 33

approx. 0.61 kg

Flange socket

3-pole GHG 511 83

approx. 0.38 kg

Wall socket 

4-pole GHG 511 44

approx. 1.50 kg

Plug

4-pole GHG 511 74

approx. 0.34 kg / GHG 531 - approx. 0.40 kg

Coupler

4-pole GHG 511 34

approx. 0.89 kg

Flange socket

4-pole GHG 511 84

approx. 0.53 kg

Wall socket  

5-pole GHG 511 45

approx. 1.55 kg

Plug

5-pole GHG 511 75

approx. 0.38 kg / GHG 531 - approx. 0.41 kg

Coupler

5-pole GHG 511 35

approx. 0.89 kg

Flange socket

5-pole GHG 511 85

approx. 0.58 kg

1.1  Auxiliary contact

Technical data

Auxiliary contact, rated voltage:

250 VAC

Auxiliary contact, rated current:

AC / 5 A

DC / 0.03 A

Explosion protected plug and socket  system 16 A, 
3-pole, 4-pole, 5-pole, GHG 511

GB

Содержание GHG 511

Страница 1: ...G 511 Explosion protected plug and socket system 16 A 3 pole 4 pole 5 pole GHG 511 Fiches et prises de 16 A 3 p les 4 p les 5 p les pour atmosph res explosives GHG 511 Betriebsanleitung Operating inst...

Страница 2: ...ions 7 3 Conformity with standards 8 4 Field of application 8 5 Use Properties 8 6 Installation 8 6 1 Mounting 9 6 2 Opening the device Electrical connection 9 6 3 Cable entries KLE blanking plugs 9 6...

Страница 3: ...5 Ex tD A21 IP 66T 80 C Flanschsteckdose GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Bemessungsspannung GHG 511 3 polig bis 415 V 50 60 Hz GHG 511 4 polig bis 690 V 50 60 Hz GHG 511 5 polig bis 690 V...

Страница 4: ...ng zu sichern Das Stecken undTrennen des Steckers von der Steckdose ist nur im ausgeschalteten Zustand m glich Nach dem Einschalten der Steckdose wird um die Schutzart gem Typenschild auch mit gesteck...

Страница 5: ...das Griffst ck eindrehen Alle Schrauben und oder Muttern der An schlussklemmen auch die der nicht benutzten sind fest anzuziehen Bei berm igem Anziehen kann der Anschluss beeintr chtigt oder besch di...

Страница 6: ...sicherstellen oder geeignete Schutzma nahmen ergreifen Die erforderlichenWartungsintervalle sind anwendungsspezifisch und daher in Abh ngig keit von den Einsatzbedingungen vom Betreiber festzulegen Im...

Страница 7: ...x de ia II CT6 bzw T5 Ex tD A21 IP 66T 80 C Flange socket GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Rated voltage GHG 511 3 pole up to 415 V 50 60 Hz GHG 511 4 pole up to 690 V 50 60 Hz GHG 511 5 po...

Страница 8: ...plug can be pushed into the socket and pulled out of it only whilst the socket is switched off In order to ensure the socket s type of protection acc to the type label also with the plug being inserte...

Страница 9: ...tive contacts When reassembling the flange screws shall be screwed into the body sleeve with a maximum test torque of 1 Nm All screws and or nuts of the supply terminals also of those remaining vacant...

Страница 10: ...s depend on the specific application and will therefore have to be determined by the user dependent on the conditions of use When servicing the plugs and sockets parti cularly those parts that are dec...

Страница 11: ...Prise bride GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Tension nominale GHG 511 3 p les jusqu 415 V 50 60 Hz GHG 511 4 p les jusqu 690 V 50 60 Hz GHG 511 5 p les jusqu 500 V 50 60 Hz Fiche GHG 543 2...

Страница 12: ...bloqu e avec l anneau ba onnette La fiche ne peut tre enfich e dans la prise ou retir e de celle ci que lorsque la prise est mise hors circuit Afin d assurer le mode de protection selon la plaque sign...

Страница 13: ...exion aussi celles des bornes non utilis es doivent tre serr es fond Afin de maintenir le mode de protection contre l explosion le raccordement des conducteurs doit se faire tr s soigneusement Les bor...

Страница 14: ...rvice requis d pendent de l emploi sp cifique et devront donc tre fix s par l utilisateur en tenant compte des condi tions d exploitation Lors de l entretien des appareils surtout les composants qui s...

Страница 15: ...liaire GHG 511 543 Ansicht 1 View 1 Voir 1 Ansicht 2 View 2 Voir 2 2 1 Schaltschema Switching operation m canisme de commutation AnschlussbildWand Flanschsteckdose GHG 511 Contact arrangementWall Flan...

Страница 16: ...nwand Inner wall of enclosure Paroi interne de l enveloppe 110 130V gelb yellow jaune 220 250V blau blue bleu 220 250V blau blue bleu 380 415V rot red rouge 500V schwarz black noir GHG 511 3 pol PE 50...

Страница 17: ...s in mm Dimensions en mm X Befestigungsma e X fixing dimensions X dimensions de fixation 2 pol PE 3 pol PE 3 p l N PE Flanschsteckdose Flange socket Prise bride 2 pol p l PE Flanschsteckdose Flange so...

Страница 18: ...e GHG 543 23 2 pol p l PE Stecker Plug Fiche GHG 531 7 4 5 pol p l PE Stecker Plug Fiche GHG 511 4 4 5 pol p l PE Stecker Plug Fiche GHG 511 43 2 pol p l PE Kupplung Coupler Prolongateur 2 pol p l PE...

Страница 19: ...19 Notizen Notes Remarques...

Страница 20: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Страница 21: ...plugs and sockets 16 A 4 pole and 5 pole GHG 511 stainless steal Fiche et prise de 16 A 4 p les et 5 p les pour atmosph res explosives GHG 511 acier inoxydable GHG 510 7001 P0012 D GB F a CROUSE HIND...

Страница 22: ...ns contact auxiliaire avec contact auxiliaire GHG 511 3 pol PE 50 60Hz 380 415V rot GHG 511 4 pol PE 50 60Hz 220 250V blau 690V schwarz 500V schwarz 380 415V rot 220 250V blau 690V schwarz 500V schwar...

Страница 23: ...eitshinweise Dieser Anhang zur Betriebsanleitung GHG 510 7001 P0012 ist immer mit der Betriebsanleitung GHG 510 7001 P0001 zu verwenden Dort aufgef hrte Hinweise sind zu beachten Die Steckvorrichtunge...

Страница 24: ...nter Ber cksichti gung einschl giger Vorschriften anzuschlie en Der Zusammenbau erfolgt nach dem Kabel anschluss in umgekehrter Reihenfolge Die minimal und maximal anschlie baren Leiterquerschnitte so...

Страница 25: ...instructions This Annex to operating instructions GHG 5107001P0012 is only for use with the original operating instructions GHG 510 7001 P0001 The GHG 511 plugs and sockets are not suitable for Zone...

Страница 26: ...crews and or nuts of the supply terminals also of those remaining vacant shall be tightened down The conductors shall be connected with special care in order to maintain the explosion category The sup...

Страница 27: ...utilis e qu avec le mode d emploi original GHG 510 7001 P0001 Les fiches et prises du type GHG 511 pour atmosph re explosive ne sont pas appropri es la zone 0 et zone 20 Respectez les prescriptions n...

Страница 28: ...tenant compte des r glements respectifs les conducteurs d ment d nud s des c bles sont raccord s Apr s le raccordement du c ble le montage se fait dans l ordre inverse Les sections minimales et maxima...

Страница 29: ...9 Notizen Notes Remarques...

Страница 30: ...10 Notizen Notes Remarques...

Страница 31: ...11 Notizen Notes Remarques...

Страница 32: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Отзывы: