62
Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
A third repeater called a Graphical Mimic Relay board has recently been added to the range
– this
device provides 8 outputs or 4 inputs depending on model
The inputs are pre programmed reset, evacuate, silence and test.
The outputs can follow Fire are programmed in the same manner as the 32 way board. See Fig 58
Each output can have up to 16 ‘rules’ This unit takes one address on the numbering sequence and is
powered by the loop.
Note. If this device is fitted on a Spur the relay functions will not operate correctly if there is a
break on spur wiring.
These Devices can not be used on CF2000
Fig 58
CIOP7273
Recent changes to BS5839 have highlighted the need to follow other relevant regulation such as
BS7273 in relation to attached equipment, for example door holders and magnets.
Fig 59