55
Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Each channel is individually programmable both for inputs and outputs in the same way as the
MIO1240.
Because this device only holds 1 address there is no way to apply text to the individual channels.
This unit contains the same restrictions concerning delays
– which can ONLY be programmed
on stage 1 of output 1
MIO324T/MIO324SST
This unit is identical in build to the MIO 324, but this has been designed to take 3 addresses (this can
be expensive in terms of outputs because it replies as 3 x 3Chan I/O’s), this means that text
information can be allocated to each channel. It also allows each individual input and output to be
disabled (by address). This has now been superceded by the MIO324SST (VDS variant) which has
the same functionality but different end of lines (680 fire resistor and 3K3 end of line).
MIO324S
Once again, this unit is identical with the MIO 324 only taking 1 address. The programming is the
same as the MIO 324. This unit was designed so that the relay outputs reset on silence rather than
full reset.
MCOM
This unit is a Mini output unit providing switch contacts only, rated at 1A 30v. There is no input on this
unit. This item replies as an I/O unit so takes 1 of the 20 I/O’s allowed per loop.
MCOM/S & ULMCOM/S
Identical to the above but this unit is programmed to reply as a sounder
,
the relay contacts on the
MCOM/S change state on reset, the UL version resets on silence. These units have been created to
enable more than the 20 relay outputs per loop by sacrificing the total amount of sounders allowed.
Note
– The MCOM/S unit must be programmed using site installer - the contacts DO NOT
change state in Autolearn
ULMCIM, ULMCIM/C, MCIM/NF
These units are a Mini input unit capable of monitoring volt-free contacts in other fire panels, sprinkler
flow switches etc. The ULMCIM replies as a I/O unit and therefore will take 1 of the 20 allowed per
loop. End of line resistance is 22K the firing resistor being 5K6.
The ULMCIM/C is identical to the above this unit replies as a Callpoint (Pullstation) so
accommodating up to 200 per loop. The response time of operation has also been modified to
operate in the same way as a Callpoint, so this item will put a fire on the panel quicker than a
standard input generated from an I/O unit.
The MCIM/NF (obsolete since 2012) is a Non-Fire input and is identical to the MCIM and MCIM/C.
This has been programmed not to indicate a FIRE condition on the panel when in alarm.
Loop outputs can be programmed to respond to this device without the need to create a fire condition
on the panel. The panel outputs DO NOT respond to this input.
MCIM (INPUT)
This device replies only as an Input and up to 200 can be installed per loop. It has been introduced to
replace all of the above mini inputs except the UL range, (because of the UL approvals) and is
programmed on Site installer for various functions as shown.
.
Fig 51
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...