40
Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
If the network is such that all messaging needs to be turned off, but certain panels need to
communicate directly with each other this can be controlled using the network filtering system where
individual panel messaging can be enabled/disabled across the network.
These features are found in ‘Network’ in the configuration menu.
Extra filtering has been added to enable the user to filter commands (reset, evacuate, silence, mute
buzzer) and Status messaging (Fires & faults) across the network
Fig 30
Day / Night Settings
This is a function in the panel programming that allows certain devices to change their characteristics
dependant on the time of day. The devices that respond to this programming are the Heat detectors
and Photo thermal.
To program day night mode on the panel you add an input device and then on the input programming
menu you tick the day night box.
Then you go to either thermal or photo thermal detectors and on the input programming menu, you
tick day night mode.
When you tick day / night on an input unit (I/O or callpoint) you are controlling when the panel goes
into and out of day / night mode.
When you tick day / night on a detector you are instructing that specific detector to respond to
day / night programming.
NOTES
The input unit in question must be either an I/O unit or a Callpoint.
If a 3 Chan I/O unit is used only channel 1 can be used for this function (the other
channels will put the panel to full fire.
The input unit must be on the same Loop Controller as the devices it is setting to Day/Night
As soon as a Photo thermal has a tick against Day/Night the detector becomes pure heat (A2S
- Fixed Heat 60). Hence the Callpoint or I/O must be operated to return this device to dual
mode.
A half-moon indication now appears on the screen between the supervisor button on the clock
when day night is in operation.
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...