EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Zone Groups and DN any zone 2 devices
To further enhance the cause and effect programming options Zone groups have now been added
into both Site installer and the latest release software (JUL 2011).
250 Zone groups have been added to the system so that when any output devices trigger source is by
zone this now becomes by zone group.
Each zone group can contain up to 32 traditional zones and each output stage can be programmed
by up to 16 zone groups.
Fig 19
In fig 19 above the output is programmed to operate by zone group and zone groups 18 is selected as
the trigger source.