EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Alarm Verification Feature
When this is set any detector that enters a fire condition will show on the panel, but no sounder
program will be activated, a 15 sec timer will start. At the end of the 15 secs, if the detector is still at
alarm level the sounders will activate. If during this time the detector has dropped below the alarm
level, then the panel will not go to alarm.
This is particularly useful to prevent false alarms from detectors where the smoke is from other
sources other than a fire i.e. smoking in bedrooms.
On later version software the AVF length can be timed from standard or long delay (30 secs) and
when in UL 864 9
th
edition mode a longer time (60 secs) has also been added.
A further option includes the addition of AVF on specific zones.
Auxiliary Board
Extra boards or additional features for other markets can be installed within the DF6000. These
include Extinguisher and Fire brigade boards to enable the control of other services within buildings in
Germany. See Fig 7a
Australian Mode creates a re-configured display screen when class change is shorted. In this mode a
key-switch device is installed on the front door of the DF6000 panel which can only be operated by
the Australian fire brigade (this key-switch shorts the class change). Address or zone text for the
alarm can be viewed on the screen depending on how the screen is configured. (See page 37)
Fig 12
The re-configured screen gives the Fireman controls to; silence the alarms, mute buzzer and reset the
panel without having access to the pass-code.
Swedish mode is very similar except that the panel must be in Swedish language for this feature to be
operational.
HMO Mode
This feature has been added to accommodate BS 5839 Part 6
– Fire Alarm Installations in Dwellings.
BS 5839 part 1 does not cover private dwellings, however, a landlord is required under this to protect
all common areas within his building, and generally this would be designed as L3 coverage with a
detector and sounder in the lobby area of the flat.
Mains or battery powered smoke detection (part 6 smoke alarms) would then be installed within the
living accommodation to provide protection but preventing a false alarm in a flat evacuating the whole
building.
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...