58
Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
MCOM-FC
A dedicated output device to work in conjunction with the Smoke Control System and FC6/18.
Due to the nature of operation this device will show as in fault from the Analogue Values screen
however this does not mean the device is in fault. In its normal working state, the device will not show
fault on the panel. It will display fault, should the device go missing or stop working correctly.
4 Way Sounder Control Unit (MPU 424/CSC354CPR)
The MPU 424 is designed to accept 4 conventional sounder circuits with a total rating of 3.2A spread
equally over the 4 outputs. This unit takes 1 address on the DF6 system and has its own power
supply and battery backup.
Version 2, CSC354CPR has been reduced to 1.6 A loading but is now an approved item
Each individual circuit can have the same programming as a single loop sounder output.
The only criteria being that a delay can ONLY be programmed on stage 1 of channel 1,
however, version 2 has a jumper to force outputs 2,3 and 4 to follow output 1.
MARDF6
Because the loop output devices cannot be programmed for fault, the MARDF6 was designed to
provide a fault relay with dry contacts for use with an Autodialler or Redcare that requires a fire and
fault signal.
This unit connects across the FRE or FPE outputs and the Fault output. The internal 24v supply in the
panel powers the unit.
Spur Isolator- MSI850
This unit is designed to accommodate a Spur of addressable devices but does not take an address
itself. If the unit is installed at the outset the panel autolearns up to this device, then autolearns the
spur and then carries on with the remainder of the loop. The spur isolator can also be added after the
panel has been autolearned but any devices on the spur MUST be added ONE AT A TIME.
If all devices are run off a number of Spur isolators, then one single device MUST be fitted on
the loop between the last isolator and the return run to the panel. (If this is not done then
‘Short circuit far’ will be displayed on the panel)
Beam Detector MAB50/100R
The reflective beam detector uses one address on the system. Initially the unit is auto learned and
then aligned using the Dill switches on the rear of the unit.
The device mode switch is set to run mode by default and the detector will not learn to the
panel if set to any other position.
Set the 3-
position switch is set to position 1 ‘Prism target Mode’ align to the prism using the
thumbscrews. Once the prism has been correctly targeted the prism MUST be covered to ensure the
device is not receiving reflections from other sources.
Set the switch to position 2 ‘Alignment Mode’ and fine-tune the alignment using the thumbscrews.
Finally, once fully aligned, set the switch to position 3 ‘Run Mode’ and reset the fire panel
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...