Sounders, beacons, sounder beacons all appear on the DF6000 device list as alarm/beacons and a
maximum of 60 are allowed per loop and set to low volume, the panel and site installer treats them all
the same for programming purposes.
The site installer allows 3 stages for the device outputs and various options can be chosen at each
stage. Delays can ONLY be used on stage 1. (There is NO hierarchy on the stages whichever setting
fulfils the requirement the sounder/beacon will comply with that setting)
The settings i.e. sound or volume for the sounders can be done globally at the panel or individually on
the site installer.
Input/output Devices
MIO1240
is a single input single output device. The output takes the form of a mains rated relay
capable of switching up to 8A.
The Input spur is used to monitor a set of volt free contacts the end of line being 22k and a firing
resistance of 5k6.
Programming of the output has the same features as the sounder outputs. The Input programming is
the same as programming for the call point.
MIO324
is a 3 channel I/O (3 separate inputs & 3 separate outputs) that only takes 1 address. The
outputs are three relays capable of switching 1A at 30v.
The 3 input spurs have the same function as the MIO1240, 22k end of line, 5k6 firing resistor.
Each channel is individually programmable both for inputs and outputs in the same way as the
MIO1240.
Because this device only holds 1 address there is no way to apply text to the individual channels.
This unit contains the same restrictions concerning delays
– which can ONLY be programmed
on stage 1 of output 1
MIO324T/MIO324SST
This unit is identical in build to the MIO324, but this has been designed to take 3 addresses (this can
be expensive in terms of outputs because it replies as 3 x 3Chan I/O’s), this means that text
information can be allocated to each channel. It also allows each individual input and output to be
disabled (by address). This has now been superceded by the MIO324SST (VDS variant) which has
the same functionality but different end of lines (680
Ω fire resistor and 3K3 end of line).
MIO324S
Once again, this unit is identical with the MIO324 only taking 1 address. The programming is the
same as the MIO324. This unit was designed so that the relay outputs reset on silence rather than full
reset.
MCOM
This unit is a Mini output unit providing switch contacts only, rated at 1A, 30v. There is no input on this
unit. This item replies as an I/O unit so takes 1 of the 20 I/O’s allowed per loop.
MCOM/S & ULMCOM/S
Identical to the above but this unit is programmed to reply as a sounder
,
the relay contacts on the
MCOM/S change state on reset, the UL version resets on silence. These units have been created to
enable more than the 20 relay outputs per loop by sacrificing the total amount of sounders allowed.
Note
– The MCOM/S unit must be programmed using site installer - the contacts DO NOT
change state in Autolearn
ULMCIM, ULMCIM/C, MCIM/NF
These units are a Mini input unit capable of monitoring volt-free contacts in other fire panels, sprinkler
flow switches etc. The ULMCIM replies as a I/O unit and therefore will take 1 of the 20 allowed per
loop. End of line resistance is 22K the firing resistor being 5K6.
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...